Toshiba 431B Manuale Utente

Pagina di 64
34
 
4300 Series Ancillary Cabinets Installation and Operation Manual
Ilsco P/N
Description
Conductor Size
Fitting Color
CLND-4/0-12-134
CSWD -4/0-12-134
Long Barrel
Short Barrel
4/0
Purple
CLND-250-12-134
CSWD -250-12-134
Long Barrel
Short Barrel
250
Yellow
CLND-300-12-134
CSWD -300-12-134
Long Barrel
Short Barrel
300
White
CLND-350-12-134
CSWD -350-12-134
Long Barrel
Short Barrel
350
Red
Go to Section 
Place the 431B Cabinet.
Table 11.3 - 431B Power Cable Sizes
(
Cable sizes for 75°C Copper Cable)
Recommended/Maximum Wire size and Torque Requirement
UPS  
Rating
Maximum DC Current
Recommended Cable 
Sizes
UPS Terminal Lug 
Tightening Torque
431B Bus Lugs 
Tightening Torque
20 kVA
84 Adc
4 AWG – 350 kcmil
200 in.-lbs.
119 ft-lb (161 N•M)
30 kVA
126 Adc
1 AWG – 350 kcmil
200 in.-lbs.
119 ft-lb (161 N•M)
40 kVA
169 Adc
1/0 – 350 kcmil
200 in.-lbs.
119 ft-lb (161 N•M)
50 kVA
210 Adc
4/0 – 350 kcmil
200 in.-lbs. 
119 ft-lb (161 N•M)
60 kVA
253 Adc
250 kcmil – 350 kcmil
200 in.-lbs.
119 ft-lb (161 N•M)
* Wire capacity for DC lugs is 350 kcmil - 6 AWG,   
11.4     Place the 431B Cabinet
The 431B Cabinet has four mounting holes to anchor the unit after is has been set in place.  See Figure 
10-3.  Use 1/2 in (12 mm) bolts to anchor the 431B.
Verify the Left Side Access Plate of the 431B and the corresponding Right side ac-
cess plate of the 4300 UPS are removed before anchoring the unit. 
NOTE: Ensure the 431B can be joined to the UPS before final anchoring of the 431A. Use four 3/8 in.
-16 x 2 in long bolts to bolt the ancillary cabinet frames together.
Back
Front
4 x 0.63 in. Dia. (16 mm)
19.0 in. (483 mm)
26.7 in..
(677 mm)
Figure 11-3 - 431B Base Anchor Points