ELECTRICAL POWER SUPPLY
Autoflow to Master Fan/Heater Unit Interconnect
       The Master Fan/Heater Unit is the only fan
and heater in a single fan unit.  In two fan units
it is the fan/heater with the airswitch, plenum
temperature sensor, and grain temperature sensor
connected to it.  DO NOT run the control wires
for the Master Fan/Heater in the same conduit
as the power wires for the fan motor.  To wire
the Master Fan/Heater Unit to the Autoflow
Control Box do the following.
                  Important!
           NOTE:  Do NOT use solid wire for
 interconnections.
NOTE:  A shielded 16 gauge cable is
recommended for use on the network
connection.  The network wires for this
configuration are attached to terminals number
4 and 5.  Ground each end of the shielded cable
to the housing.  A shielded 16 gauge 2 wire cable
can be purchased from GSI.  Part # WR-16 /
2S.
1)
Run five (5) control wires from the
Autoflow Control Box to the Master
Fan/Heater Unit.
2)
Connect the wires as shown in figure 19.
Figure 19