Section 4  User Interface Guide
Total Access 600 Series System Manual
 74
© 2004 ADTRAN, Inc.
61200624L1-1B
I
NTERFACES
 (T1) > S
TATUS
 > A
LARMS
 > C
URRENT
 A
LARMS
Displays the current alarms on the T1 interface. An asterisk in a field indicates that an alarm is active.
I
NTERFACES
 (T1) > S
TATUS
 > A
LARMS
 > A
LARM
 H
ISTORY
Displays the alarm history for the T1 interface. An asterisk in a field indicates that an alarm has occurred 
on the T1 interface since the last clear history. Refer to Interfaces (T1) > Status > Alarms > Current 
Alarms
 for more details on listed 
alarm conditions.
I
NTERFACES
 (T1) > S
TATUS
 > A
LARMS
 > C
LEAR
 H
ISTORY
Selecting this activator will clear the Alarm History for the T1 interface.
I
NTERFACES
 (T1) > S
TATUS
 > R
X
 L
EVEL
Displays the level (in dB) of the received T1 signal on the interface.
I
NTERFACES
 (T1) > T
EST
These options are used to initiate local and remote loopback tests and display the test status.
I
NTERFACES
 (T1) > T
EST
 > L
OC
 LB
Loopback of the local unit. Choices are 
N
ONE
,
 L
INE
,
 
and
 P
AYLOAD
L
INE
 loopback loops all of the received 
data back toward the network. The transmitted data is the identical line code that was received, including 
any bipolar violations. 
L
INE
 loopbacks tests right up to the T1 interface of the ADTRAN unit. 
P
AYLOAD
 
loopback is similar to line loopback except that the framing is extracted from the received data and then 
regenerated for the transmitted data. 
P
AYLOAD
 loopbacks not only verify the T1 circuit, but also the internal 
hardware of the local ADTRAN device. 
N
ONE
 disables the loopback test. Default is 
N
ONE
.
I
NTERFACES
 (T1) > T
EST
 > R
EM
 LB
Sends a loopback command across the network to a remote unit over the FDL, which causes the remote 
unit initiate a local 
L
INE
 or 
P
AYLOAD
 loopback (whichever is specified). The remote loopback is only 
available when the T1 is configured for ESF mode.
I
NTERFACES
 (T1) > T
EST
 > T
EST
 S
TATUS
 
Indicates whether a test is in progress.
LOS
Loss of Signal. No signal detected on port interface.
RED
Not able to frame data received on the port. Alternately referred to as Out of 
Frame (OOF). RED alarm most frequently occurs when there is a framing 
mismatch on the T1 interface.
YELLOW
Remote alarm indicator (RAI) being received on port. A YELLOW alarm indicates 
that the remote unit is not receiving properly framed information from your unit. 
BLUE
Receiving unframed all ones from the port alarm indicator signal (AIS). A BLUE 
alarm is sent to notify the unit that equipment upstream is disconnected or 
malfunctioning.