1 Install and cable a G600 cabinet
Install equipment-room hardware for G600
94
S8100 Installation and Upgrades
November 2003
Sneak-current protectors must have a maximum rating of 350 mA and a minimum voltage rating of 600V, 
or as required by local regulations. The following devices protect the system from over-voltages:
Analog trunks use the 507B sneak protector or equivalent. Over-voltage protection is normally 
provided by the local telephone company.
Analog voice terminals use one of the following types of combined over-voltage and sneak-
current protection, or equivalent:
— Carbon block with heat coil for UL code 4B1C
— Gas tube with heat coil for UL code 4B1E-W
— Solid state with heat coil for UL code 4C1S
DCP and ISDN-BRI terminals use the solid state 4C3S-75 with heat coil protector, or equivalent.
DS1/T1 circuits require isolation from exposed facilities. This isolation may be provided by a 
channel-service unit (CSU) (T1), or other equipment that provides equivalent protection.
Install sneak fuse panels
Sneak-current protection is required between the incoming RJ21X or RJ2GX network interface and the 
system for both trunk and off-premises circuit packs. The model 507B sneak-current fuse panel, or 
equivalent, is recommended for sneak-current protection. See 
Figure 20: Model 507B sneak fuse panel
Figure notes
1
507B sneak-current protector 
(comcode 107435091)
2
25-pair male connector (in) 
(comcode 846300994)
3
25-pair female connector (out) (comcode 
846300994)
4
220029 fuses (inside panel) – Use a small 
screwdriver to pry top cover off.
Sneak
Current
Protector
507B