Mitsubishi Electronics Q68RD3-G ユーザーズマニュアル

ページ / 212
3
 - 30
3.4 Buffer Memory
3.4.2 Conversion enable/disable setting (Un\G0)
3
SPECIFICATIONS
3.4.2
Conversion enable/disable setting (Un\G0)
(1) Temperature conversion enable/disable status is set for each channel.
(2) Setting "Disable" for unused channels can prevent unnecessary 
disconnection detection.
(3) The default value is set to "Disable" for all channels.
[Example]
(4) To activate the setting, turning ON/OFF Operating condition setting 
request (Y9) is required.
b15
b14
b13
b12
b11
b10
b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
CH8 CH7 CH6 CH5 CH4 CH3 CH2 CH1
0
0
0
0
0
0
0
0
Data for b8 to b15 are fixed to "0".
0: Enable
1: Disable
b15
b14
b13
b12
b11
b10
b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
Channel 1 and 2 are enabled for conversion.