Mitsubishi Electronics Q68RD3-G ユーザーズマニュアル
3
- 32
3.4 Buffer Memory
3.4.4 Conversion completion flag (Un\G10)
3.4.4 Conversion completion flag (Un\G10)
3
SPECIFICATIONS
3.4.4
Conversion completion flag (Un\G10)
(1) The bit of the corresponding channel in the Conversion completion flag
turns ON (changes to "1") when conversion of conversion-enabled
channels is completed.
When averaging processing is specified, the flag turns ON (changes to
"1") after the first averaged value is stored into the CH Measured
temperature value (Un\G11 to Un\G18).
Conversion completion flag (XE) turns ON when conversion of all
conversion-enabled channels is completed.
channels is completed.
When averaging processing is specified, the flag turns ON (changes to
"1") after the first averaged value is stored into the CH Measured
temperature value (Un\G11 to Un\G18).
Conversion completion flag (XE) turns ON when conversion of all
conversion-enabled channels is completed.
(2) When Operating condition setting request (Y9) is turned ON, the bit
returns to the default value of OFF ("0") and it turns ON ("1") after
conversion is completed.
conversion is completed.
(3) If disconnection is detected in the status where the bit of each channel
in the Conversion completion flag (Un\G10) has already been ON ("1"),
the bit remains ON ("1").
the bit remains ON ("1").
(4) Use this area or the Conversion completion flag (XE) as an interlock to
read out the measured temperature value.
b15
b14
b13
b12
b11
b10
b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
CH8 CH7 CH6 CH5 CH4 CH3 CH2 CH1
0
0
0
0
0
0
0
0
Data for b8 to b15 are fixed to "0".
0: During conversion or unused
1: Conversion completed
1: Conversion completed