3.4 Buffer Memory
3.4.6 Error code (Un\G19)
3
SPECIFICATIONS
3.4.6
Error code (Un\G19)
(1) Error code that is detected by the Q68RD3-G is stored.
(2) For details on error codes, refer to Section 8.1.
3.4.7
Setting range 1, 2 (Un\G20 and Un\G21)
(1) This area is for checking the measurement range of the Q68RD3-G, 
which is set with Switch 1 and 2 in the intelligent function module switch 
setting.
Setting values of the measurement range are stored into the area 
indicated below for each channel.
(2) The following table shows the measurement range and setting value for 
each RTD.
3.4.8
Setting range 3 (Offset/gain setting) (Un\G22)
(1) This area is for checking the offset/gain setting of the Q68RD3-G, which 
is set with Switch 3 in the intelligent function module switch setting.
"0" is stored for factory default setting and "1" is stored for user range 
setting.
Table 3.11 Measurement range and setting value
RTD
Measurement range
Setting value
Pt100
-200 to 850
0
H
-20 to 120
1
H
  0 to 200
4
H
JPt100
-180 to 600
2
H
-20 to 120
3
H
0 to 200
5
H
Ni100
-60 to 180
8
H
b0
Un\G20 
(Setting range 1 CH1-4)
Un\G21 
(Setting range 2 CH5-8)
b15
b12 b11
b8 b7
b4 b3
CH4
CH3
CH1
CH8
CH7
CH6
CH5
CH2
to
to
to
to
b15
b14
b13
b12
b11
b10
b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
CH8 CH7 CH6 CH5 CH4 CH3 CH2 CH1
0
0
0
0
0
0
0
0
Data for b8 to b15 are fixed to "0".
0: Factory default setting
1: User range setting