Gas Requirements
37
M414905
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Gas Supply Pipe Sizing and Looping
Figure 19 
TMB2126N
1
Gas furnace (120,000 Btu/hr.)
7
Minimum Pipe Size is 0.5 in. (12.7 mm)
2
Gas water heaters (400,000 Btu/hr. each)
8
25 ft. (7.6 m)
3
Gas space heaters (70,000 Btu/hr. each)
9
Main regulator
4
Sediment traps, supply pressure taps and 
10
Gas meter
shut-off valves. Refer to Figure 18.
11
Pressure regulator (if required)
5
1 in. (25.4 mm) gas pipe loop
12
50 pound tumblers (120,000 Btu/hr each)
6
19 ft. (5.8 m)
75 pound tumblers (165,000 Btu/hr each)
F75 pound tumblers (215,000 Btu/hr each)
SAMPLE CALCULATIONS:
Equivalent length =  Total length of main gas supply pipe to the far end of the tumblers.
=  25 ft. + 19 ft. (7.6 m + 5.8 m) gas supply pipe
=  44 ft. (13.4 m) Total Gas Line
Total Btu/hr. 
=  The sum of the Btu/hr. of all 50 pound tumblers being fed by the main gas supply pipe.
= 9 x 120,000
= 1,080,000 Btu/hr.
Using Table 5, the main supply pipe diameter should be 2 in. (51 mm).
IMPORTANT: Gas loop piping must be installed as illustrated to equalize gas pressure for all tumblers 
connected to single gas service. Other gas using appliances should be connected upstream from loop.