Mitsubishi Electronics Q173CPU(N) ユーザーズマニュアル

ページ / 472
 
 
 
11 - 8 
11   MOTION SFC PARAMETER 
 
11.4 Task Parameters 
 
No. Item 
Setting 
item 
Initial 
value  Remark 
Number of 
consecutive 
transitions 
Normal task 
(Normal task 
common) 
1 to 30 
2 Interrupt 
setting 
Set whether the event 
task or NMI task is 
used for external 
interrupt inputs  
(I0 to I15). 
Event task 
These parameters are imported 
when PLC ready flag (M2000) 
turns off to on and used for control 
thereafter. 
When setting/changing the values 
of these parameters, turns the 
PLC ready flag (M2000) off. 
 
(1)   Number of consecutive transitions 
[Description] 
With "execution of active step   judgment of next transition condition   
transition processing performed when condition enables (transition of active 
step)" defined as a single basic operation of the Motion SFC program execution 
control in the execution cycle of the corresponding task, this operation is 
performed for the number of active steps to terminate processing once. And the 
same operation is processed continuously in the next cycle. 
In this case, the transition destination step is executed in the next cycle when the 
transition condition enables. 
 
Consecutive transition control indicates that transition destination steps are 
executed one after another in the same one execution cycle when their transition 
conditions have enabled (single basic operation is performed consecutively). 
In this case, the number of consecutive transitions can be set. 
Controls in common to the Motion SFC programs executed by normal tasks. 
 
POINT 
 
Set the number of consecutive transitions to the Motion SFC programs executed 
by event and NMI tasks for every program. 
 
 
[Errors] 
These parameters are imported and checked when the PLC ready flag (M2000) 
turns off to on. 
When the value that was set is outside the setting range, the following Motion 
SFC error is set and the initial value is used to control. 
 
Error cause 
Error code 
(Note)
 
Name Contents 
Error processing
Corrective action 
17000 
Normal task 
consecutive 
transition 
count error 
The normal task's 
consecutive transition 
count of the Motion SFC 
program executed by the 
normal task is outside the 
range 1 to 30. 
The initial value 
of 3 is used for 
control. 
Turn PLC ready flag (M2000) 
off, make correction to set the 
value of within the range, and 
write it to the CPU. 
(Note) : 0000H (normal)