11   MOTION SFC PARAMETER 
 
11.5 Program Parameters 
Set the following parameters for every Motion SFC program. 
 
No. Item 
Setting 
range 
Initial 
value
Remark 
1  Start setting 
Automatically started or not 
Not setting 
It is only one of normal, event and NMI tasks 
Normal task
When you have set the event task, further set the 
event which will be enabled. 
Always set any one of the following 1 to 3. 
 1. Fixed cycle  
It is one of 0.88ms, 1.77ms, 3.55ms, 7.11ms and 
14.2ms or none. 
 2. External interrupt (make selection from those set 
to event task) 
Multiple interrupt can be set from among I0, I1, I2, 
I3, I4, I5, I6, I7, I8, I9, I10, I11, I12, I13, I14 and 
I15. 
 3. PLC interrupt  
Multiple interrupt can be set from among I0, I1, I2, 
I3, I4, I5, I6, I7, I8, I9, I10, I11, I12, I13, I14 and 
I15. 
1 to 3 can be set also by OR.  
(A duplication setting is possible.) 
The same event can be shared among multiple 
Motion SFC programs. 
2 Execute 
task 
When you have set the NMI task, further set the 
interrupt input which will be enabled. 
 1. External interrupt (make selection from those set 
to NMI task) 
Multiple interrupt can be set from among I0, I1, I2, 
I3, I4, I5, I6, I7, I8, I9, I10, I11, I12, I13, I14 and 
I15. 
None 
Number of 
consecutive 
transitions 
1 to 10 
Set the number of consecutive transitions toward the 
program set to the event or NMI task. 
END 
operation 
End/continue  
Set the operation mode of the END step toward the 
program set to the event or NMI task. 
End 
These parameters are imported 
at starting of the PLC ready flag 
(M2000) and used for control 
there after. 
When setting/changing the 
values of these parameters, 
turn PLC ready flag (M2000) 
off. 
 
 
POINT 
 
The settings of "END operation" are invalid for the subroutine called program. 
"END operation" is controlled as "end".