3   COMMON PARAMETERS 
 
3.2.3 I/O number setting 
Set the modules installed in the each slot of the main base or extension base and 
assign the control CPU of applicable slot as the self CPU in the system setting for 
Motion CPU. 
The following modules must be set the I/O No.. 
• Input module                   • Output module 
• Input/Output composite module  
• Analogue input module   • Analogue output module 
Refer to the help of MT Developer for the detailed operating procedure on the system 
settings screen. 
 
Set the I/O No. of modules controlled with the Motion CPU module set in the system 
structure screen of MT Developer. The setting procedure of I/O No. is shown below. 
 
(Example) For set the output module 
1) Double-click the slot position, display
    the Motion Slot Settings screen.
<System Structure>
2) Select the I/O module.
5) Select applicable module type 
    and number of points for 
    the I/O module to be used.
3) Click [Detail Setting].
4) Set the first I/O No. 
    (PX No., PY No.).
6) Click [OK].
<Motion Slot Settings>
<I/O Module Settings>
 
(Note): Display of system setting and motion slot setting are different depending on the operating system 
software. 
 
POINT 
 
I/O No.s cannot be assigned automatically, unlike a PLC CPU for which I/O No. are 
assigned automatically if such setting is omitted in the Motion CPU. In the Motion 
CPU, be sure to set the first I/O No. in System Settings for each module used.