Emerson MC68HC16Z1 ユーザーズマニュアル

ページ / 48
System and Control Options
24
Figure 16 shows the main options available from the System & Control menu.
Figure 16 Menu overview - System and Control menu 
Opening Screen
LIQUI-TECT PANEL
DD-MON-YY HR:MM:SS
VERSION  X.X.X
PRESS
=STATUS/SETUP
Main Menu
VIEW STATUS
> SYSTEM AND CONTROL
↑↓
=NEXT
=SELECT
Login Screen
LOGIN
AAAA
↑↓
=SELECT
=NEXT/END
Setup System
> SETUP SYSTEM
RESET LATCHED ALARM
CLEAR ALARM HISTORY
CLEAR ZONE TREND
See
Section
SETUP ZN1 ZONE 1
SETUP ZN2 ZONE 2
SETUP ALARM OUTPUTS
SETUP REALARM DELAY
SETUP MAPMODE
SETUP SYSTEM INFO
Reset Latched Alarm
SETUP SYSTEM
> RESET LATCHED ALARM
CLEAR ALARM HISTORY
CLEAR ZONE TREND
See
Section
Reset Latched Alarms
RESET LEAK & FAULT
LATCHED ALARMS? Y
↑↓
=Y/N
=END
System & Control options
Clear Zone Trend
SETUP SYSTEM
RESET LATCHED ALARM
CLEAR ALARM HISTORY
> CLEAR ZONE TREND
See
Section
Clear Zone Trend
CLEAR ZONE TREND
ARE YOU SURE? Y
↑↓
=Y/N
=END
Clear Alarm History
SETUP SYSTEM
RESET LATCHED ALARM
> CLEAR ALARM HISTORY
CLEAR ZONE TREND
See
Section
Clear Alarm History
CLEAR ALARM HISTORY
ARE YOU SURE? Y
↑↓
=Y/N
=END
Setup Zone 1 Menu
SETUP ZN1 ZONE 1
CONNECTED:  N
LABEL: ZONE 1
UNITS: FT
AUTO CALIBRATE
WATER DETECT:150 UA
CONTAMINATED:050 UA
See
Section
Setup Mapmode
SELECT ZONE TO MAP
> ZN1 ZONE 1
ZN2 ZONE 2
VIEW LAST MAP
See
Section
Mapping Options
MAPPING ZN1 ZONE 1
CURRENT:
0UA
DISTANCE:
----
ENTRIES:0
ESC=EXIT
Setup System options
Setup System Info
SETUP SYSTEM INFO
CHANGE PASSWORD
CHANGE DATE & TIME
FACTORY DEFAULTS
See
Section
Setup Zone 2 Menu
SETUP ZN2 ZONE 2
CONNECTED:  N
LABEL: ZONE 2
UNITS: FT
AUTO CALIBRATE
WATER DETECT:150 UA
CONTAMINATED:050 UA
See
Section
Setup Alarm Outputs
SELECT LONGEST
CABLE CONNECTED
> 0-500FT (0-152.4 M)
0-1000FT (0-304.8M)
0-1500FT (0-472.2M)
0-2000FT (0-609.6M)
0-2500FT (0-762.0M)
0-3000FT (0-914.4M)
0-4000FT(0-1219.2M)
0-5000FT(0-1524.0M)
See
Section
Normally Open / Closed
ARE LEAK & FAULT
RELAYS NORMAL OPEN
OR NORMAL CLOSED? NO
↑↓
=NO/NC
=END
Latched / Unlatched
IS LEAK & FAULT
ALARM LATCHED? Y
↑↓
=Y/N
=END
Change Password
Change Date & Time
Factory Defaults
CHANGE PASSWORD
        AAAA
See
Section
CHANGE DATE & TIME
DAYLIGHT SVG TIME: Y 
18-MAY-02 10:56:30 
See
Section
RESTORE ALL DEFAULTS
ARE YOU SURE? N
See
Section
Change Realarm Delay
CHANGE REALARM DELAY
5 MINUTES
↑↓
=SELECT
=END
See
Section
Setup System Info options