D9112B | Program Entry Guide | 8.0  Point Assignments 
EN | 81 
 
 
Bosch Security Systems | 2/04 | 74-06145-000-D 
 
Point Text 
Default: 
Command 9 
Selection: 
Up to 16 characters alphanumeric 
Enter alphabetic characters A to Z 
in capital letters 
Note: 
Period (.), comma (,), percent (%), parenthesis [()], 
equal (=), greater/less than (< >), exclamation (!), 
and colon (:) are not allowed. 
Enter up to 16 characters of text to describe the 
Command 9 function. This point text is displayed at 
command centers (if the point is programmed as 
“visible”) and reported to the D6500 when 
transmitting in Modem II ( if it is a reporting point). 
8.3 Command 
The Command 7 section defines how the Command 7 
function operates. Program this section if 
User Cmd 
7
 is enabled in the User Interface module. 
This function generates an 
Alarm
 report from the 
area where the command center is assigned. A new 
report is generated each time it is activated, but only 
one alarm appears in the alarm memory count at the 
local area command centers. If this function is 
activated in more than one area within the scope of 
the command center, the alarm memory count is 
increased. 
Point Index 
Default: 
Selection: 
Blank or 00 to 31 
Enter the 
Point Index
 code used with Command 7. 
0101
0101
0101
 
 
Point Index 00 (or blank) only works with 
Command 7 and Command 9. It is a silent, 
invisible, reporting point. Point Index 00 
disables a normal point. 
 
0101
0101
0101
 
 
Do NOT use a point index with Resettable 
programmed YES. 
Do NOT use a point index with Swinger 
Bypass programmed YES. 
BFSK Code 
Default: 
Selection: 
Blank or 0 to 9 
Use this entry to determine the point number 
reported in BFSK when this point is tripped. 
Normally, you only use this item when transmitting 
reports to the central station in BFSK format. 
Command centers and local printers display the 
actual point number (1 to 135) not the BFSK report 
code. 
Activating Relays: To activate a relay on the 
D8129 OctoRelay or C8137 Transmitter Interface, 
see Relays 
A# Command 7
Point Text 
Default: 
Command 7 
Selection: 
Enter alphabetic characters A to Z 
in capital letters 
Note: 
Period (.), comma (,), percent (%), parenthesis [()], 
equal (=), greater/less than (< >), exclamation (!), 
and colon (:) are not allowed. 
Enter up to sixteen characters of text to describe the 
Command 7 function. This point text is displayed at 
command centers (if the point is programmed as 
“visible”) and reported to the D6500 when 
transmitting in Modem II ( if it is a reporting point).