D9112B | Program Entry Guide | 9.0  Relay Parameters 
EN | 82 
 
 
Bosch Security Systems | 2/04 | 74-06145-000-D 
 
9.0 Relay 
Parameters 
Relays provide basic alarm system functions (such as 
Bell Output and Reset Sensors) as well as a number 
of more advanced functions typically used in 
association with system annunciation devices. 
Up to three on-board voltage-output relays can be 
installed on the D9112 circuit board. (see the D9112 
Operation and Installation Manual
 for instructions). 
The D9112 can also control up to 128 dry contact 
form “C” relays when optional D8129 OctoRelay 
Modules are installed. 
One relay is provided with the D9112 to provide a 
+12 VDC Alarm Bell output from the D9112 
terminal 6 (Relay A). 
Two additional optional relay sockets are provided 
with the D9112. The D9112 provides a +12 VDC 
Alternate Alarm output from terminal 7 (Relay B), 
and a +12 VDC Switched Aux Power output from 
terminal 8 (Relay C). Optional relay sockets require 
Bosch Security Systems D136 Relays. 
If relay activity is reported to the receiver (see Phone 
Routing
), on-board relays are reported as follows: A 
= 253, B = 254, C = 255. 
Up to sixteen D8129 OctoRelay Modules can be 
connected to the D9112 to provide 128 dry contact 
form “C” relays. You can set DIP switches on each 
D8129 to use a group of eight numbered relays as 
shown in the D9112 Operation and Installation Manual
0101
0101
0101
 
 
Check relay status after reprogramming or 
resetting the panel. All relays are turned off 
after the panel is reset. Certain relay 
functions are checked by the panel each 
minute and resume the correct state after 
the reset. Other relays must be manually set 
to the correct state (using Cmd 54). 
 
 
Table 32: Relay Status 
 
 
Resumes Proper State 
within 1 min. 
Functions must be 
manually reset with 
Command 54 
Alarm Bell 
Late to Close 
Perimeter Fault 
Command 9 
Summary Fire 
Force Armed 
Summary Trouble 
Duress 
Printer 18 Fail 
Command 7 
Communications Fail 
Log % Full 
Silent Alarm 
 
Fire Bell 
 
AC Fail 
 
Summary Alarm 
 
Keypad Fail 
 
Printer 19 Fail 
 
Area Armed 
 
Watch Mode 
 
Area Fault 
 
Battery Trouble 
 
Summary Fire Tbl 
 
Printer 17 Fail 
 
Phone Fail 
 
Relay Follows Point 
 
Reset Sensors