Operation 
SDC / DHC  
110 EN2H-0221GE51 
R0808 
5.4.13  "Cascading" menu (CASCADE) 
The parameters in this menu refer solely to the parameters that 
are associated with the cascading of multiple heat generators.  
This selection is only available if multiple heat generators exist in 
the control system. 
 
Para-
meter 
Designation 
Setting range / Setting values 
Factory 
setting 
Setting 
01 Switching 
differential 
0.5... 30 K 
 
02 
Connection delay 
0 ... 200 min 
 
03 
Switch-off delay 
0 ... 60 min 
 
04 Switchover 
power 
of stage sequence 
10 ... 100 % 
65 
 
05 
Stage reversal  
OFF, 1 to 250 h 
OFF 
 
06 
Guidance stage 
1 ... maximum number of stages 
 
07 
Peak-load stage 
OFF, 2 ... maximum number of 
stages 
All heat generators are numbered 
consecutively within the cascade. 
The total quantity determines the 
maximum number of stages.  
OFF  
08 
Switchover of base 
load with grouping 
OFF, ON 
OFF 
 
09 Quick 
hot-water 
connection 
OFF, 1 ... maximum number of 
stages 
OFF