Honeywell EN2H-0221GE51 R0808 ユーザーズマニュアル
Operation
SDC / DHC
110 EN2H-0221GE51
R0808
5.4.13 "Cascading" menu (CASCADE)
The parameters in this menu refer solely to the parameters that
are associated with the cascading of multiple heat generators.
are associated with the cascading of multiple heat generators.
This selection is only available if multiple heat generators exist in
the control system.
the control system.
Para-
meter
meter
Designation
Setting range / Setting values
Factory
setting
setting
Setting
01 Switching
differential
0.5... 30 K
8
02
Connection delay
0 ... 200 min
0
03
Switch-off delay
0 ... 60 min
0
04 Switchover
power
of stage sequence
10 ... 100 %
65
05
Stage reversal
OFF, 1 to 250 h
OFF
06
Guidance stage
1 ... maximum number of stages
1
07
Peak-load stage
OFF, 2 ... maximum number of
stages
stages
All heat generators are numbered
consecutively within the cascade.
The total quantity determines the
maximum number of stages.
consecutively within the cascade.
The total quantity determines the
maximum number of stages.
OFF
08
Switchover of base
load with grouping
load with grouping
OFF, ON
OFF
09 Quick
hot-water
connection
OFF, 1 ... maximum number of
stages
stages
OFF