5.4.14  "Data bus" menu (BUS) 
The parameters in this menu refer solely to the parameters that 
are associated with the data bus. 
 
Para-
meter 
Designation 
Setting range / Setting values 
Factory 
setting 
Setting 
01 Central 
device 
address 
10, 20, 30, 40, 50 
10 
 
1 Expanded 
access 
authorisation 
02 Bus 
authorisation 
SDW 30 of direct 
heating circuit 
2 Simple 
access 
authorisation 
1  
1 Expanded 
access 
authorisation 
03 Bus 
authorisation 
SDW 30 of mixed 
heating circuit 1 
2 Simple 
access 
authorisation 
1  
1 Expanded 
access 
authorisation 
04 Bus 
authorisation 
SDW 30 of mixed 
heating circuit 2 
2 Simple 
access 
authorisation 
1  
 
 
5.4.15  "Relay test" menu (RELAY TEST  ) 
In this menu, the relays contained within the central device can be 
selected via the input button and checked for operation. 
 
Para-
meter 
Designation 
Setting range / Setting values 
Factory 
setting 
Setting 
01 
Heat generator test  Different relay switching sequence 
depending on the set heat 
generator 
–  
02 Direct 
heating 
circuit pump test 
OFF-ON-OFF OFF 
 
03 Mixed 
heating 
circuit pump 1 test 
OFF-ON-OFF OFF 
 
04 
Mixer motor 1 test  STOP-OPEN-CLOS 
STOP 
 
05 Mixed 
heating 
circuit pump 2 test 
OFF-ON-OFF OFF