Honeywell EN2H-0221GE51 R0808 ユーザーズマニュアル

ページ / 258
SDC / DHC 
Operation 
EN2H-0221GE51 R0808 
113 
5.4.17  "Error messages 2" menu (ALARM 2)  
Only in conjunction with heat generator interface 
Error messages triggered by an automatic stoker are displayed in 
this menu. The fault memory can hold max. 20 messages, which 
can be displayed individually. 
For this purpose, parameter 28 in the "System parameters" menu 
must be set to ON. 
 
Para-
meter 
Designation 
Setting range / Setting values 
Factory 
setting 
Setting 
01 
Error message 1 
Last error message 
"Display" 
 
02 
Error message 2 
Last error message but one 
"Display" 
 
03 
Error message 3 
Last error message but two 
"Display" 
 
04 
Error message 4 
Last error message but three 
"Display" 
 
... 
20 
Error message 20 
First error message 
"Display" 
 
21* Reset 
error 
messages 
SET by pressing the input button  – 
 
 
* OEM 
5.4.18  "Sensor calibration" menu (SENSOR ADJ.) 
In this menu, all sensors connected to the central device can be 
corrected by ±5 K based on the factory calibration value.  
 
Para-
meter 
Designation 
Setting range / Setting values 
Factory 
setting 
Setting 
01 
Outside sensor 
–5 ... +5 K 
 
02 Heat 
generator 
sensor 
–5 ... +5 K 
 
03 
Hot-water sensor 
–5 ... +5 K 
 
04 
Flow sensor of 
mixed heating 
circuit 1 
–5 ... +5 K 
 
05 
Flow sensor of 
mixed heating 
circuit 2 
–5 ... +5 K