Hydraulic Components 
SDC / DHC  
138 EN2H-0221GE51 
R0808 
7.1.11  Modulation of integral action time Tn 
The integral part (= adjustment time) determines the dynamic 
behaviour of the controller and thus the time required by the 
controller to adjust for the actual control deviation. The adjustment 
time is independent of the amount of deviation. 
 
7.1.12  Modulation of runtime 
This function allows adjusting the actuator, with regard to its finite 
running time, to the control characteristics, meaning that actuators 
with different runtimes react to the same deviation by readjusting 
by the same amount through adapting the action times. The 
integral action time Tn remains unchanged in this. However, care 
must be taken that the latter must always exceed the runtime of 
the respective actuator. 
 
7.1.13  Modulation of start time 
The start time parameter determines the length of the start-up 
phase in modulation mode so that a stable start-up is ensured. As 
soon as the set start time has expired, the modulation switches to 
its normal control characteristics defined by the modulation 
parameters.