7.1.14 Modulation
of start power
The start power parameter determines a percentage setting for
part of the modulation runtime during the start-up phase. With a
setting of 0% the actuator valve remains always closed. As soon
as the set start time has expired, the modulation switches to its
normal control characteristics defined by the modulation
parameters.
part of the modulation runtime during the start-up phase. With a
setting of 0% the actuator valve remains always closed. As soon
as the set start time has expired, the modulation switches to its
normal control characteristics defined by the modulation
parameters.
100%
42 s
60 s
90 s
t (s)
70%
t (s)
x
a
b
c
d
g
f
e
a Modulation
e Base
load
b Upward/downward
modulation
depending on the control deviation
f On
c Adjustment
operation
g Start
d Start-up phase
x Starting load (%)