7.1.14 Modulation 
of start power 
The start power parameter determines a percentage setting for 
part of the modulation runtime during the start-up phase. With a 
setting of 0% the actuator valve remains always closed. As soon 
as the set start time has expired, the modulation switches to its 
normal control characteristics defined by the modulation 
parameters. 
100%
42 s
60 s
90 s
t (s)
70%
t (s)
x
a
b
c
d
g
f
e
 
 
a Modulation 
e  Base 
load 
b Upward/downward 
modulation 
depending on the control deviation 
f On 
c Adjustment 
operation 
g Start 
d  Start-up phase 
x  Starting load (%)