Honeywell EN2H-0221GE51 R0808 ユーザーズマニュアル

ページ / 258
SDC / DHC 
Hydraulic Components 
EN2H-0221GE51 R0808 
141 
7.1.16  Use of boiler sensor 2  
Two single-stage heat generators 
For sensing of the temperature in the second heat generator with 
double boilers or two single-stage heat generators (see "Heat 
Generator" menu, parameter 1 boiler type = 3) 
 
Two measuring points in the combustion chamber 
In order to reduce standby losses by increasing the burner 
runtimes. With automatic sensor switching between boiler sensor 
1 and 2 after the burner switching cycle, the On signal for the 
burner will be determined by the upper sensor (BS1) and the Off 
signal by the lower sensor (BS2) based on the specified demand 
value and switching differential(s). 
 
7.1.17  External heat generator cut-off 
If the assigned variable input is short circuited, there will be a 
permanent deactivation of the heat generator. It is cancelled 
again once the short-circuit is remedied. 
 
 ATTENTION 
This function is meant exclusively for external override 
signals and not for safety switch off! 
 
7.1.18  Heat generator forced discharge 
When the temperature in the heat generator exceeds the set 
maximum temperature limit, any excess energy is dissipated into 
circuits downstream. This function applies to all controllers on the 
bus system. 
 
OFF 
No heat dissipation 
 
Dissipation into hot-water tank 
With provision tanks only 
 
 ATTENTION 
Thermal mixing valve at water heater outlet obligatory 
because of scalding hazard. 
Function
Function
Function
Set values