Hydraulic Components 
SDC / DHC  
162 EN2H-0221GE51 
R0808 
Differences that can be balanced by installing a wall device (see 
available accessories) may occur between the measured room 
temperature in the inhabited area and the desired room 
temperature. 
7.3.1.2  Heating curve setting (heating curve)  
Press and hold the input button for 3 seconds to access the 
"Heating Curve" menu. 
 
x
y
a
 
The slope of the heating curve describes the relation between the 
change in the flow temperature and the change in the outside 
temperature. With a larger heating surface, such as with floor 
heaters, the heating curve has a less extreme slope than with a 
smaller heating surface (e.g. radiators). 
The set value refers to the lowest outside temperature used for 
heat demand calculation. 
This parameter is to be set by the technician and should not be 
altered anymore. 
The setting of the heating curve should be carried out only in 
small steps and at adequately long intervals so that a stable 
condition can be set. We recommended making any corrections in 
0.1 – 0.2 steps after 1 – 2 days. 
 