Hydraulic Components 
SDC / DHC  
164 EN2H-0221GE51 
R0808 
7.3.1.3 Reduced 
operation 
See 5.2.5.1 Reduced operation, Pg. 79 
7.3.1.4 Heating 
system 
See 5.2.5.2 Heating system, Pg. 80 
7.3.1.5  Heating circuit temperature limit  
This function is not active if the heating circuit control is used as 
constant control (CC). 
 
This function limits the flow temperature of a heating circuit. The 
minimum and maximum temperatures set in the relevant 
parameters of a heating circuit do not exceed or fall below the 
setpoints. 
Minimum temperature limitation is not active: 
•  in case of switch-off in standby mode above the frost 
protection limit 
•  in case of switch-off in reduced automatic mode with the 
activated ECO function above the frost protection limit 
•  in case of switch-off in continuously reduced mode with 
activated ECO function 
•  in case of automatic summer switch-off 
 
•  Floor minimum limit 
•  Ventilation pre-adjustment (warm air curtain) 
•  Convector heating 
 
 ATTENTION 
To protect the floor heating systems against accidental 
overheating (malfunction - manual mode) a controller-
independent maximum temperature limit must be provided. 
For this purpose, we recommend a strap-on thermostat, the 
switching contact of which is looped through the control 
phase of the respective heating circuit pump. The thermostat 
is to be set to the maximum permissible system temperature. 
 
5.4.4 "Direct heating circuit" menu (UNMIXED CIRC), Pg. 92 
 
NOTE
Function
Application
See also