Hydraulic Components 
SDC / DHC  
168 EN2H-0221GE51 
R0808 
On the start day, heating to 25°C is carried out until midnight. The 
first day of floor covering heating starts at midnight of the 
following day. 
t
T
VLSoll
40
35
30
25
ST 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
[˚C]
 
Maximum temperature setting = 40°C. 
Progression of screed function over time with floor covering 
heating. 
 
7.3.2  Heating circuit constant temperature control  
This function must be activated in the "Hydraulics" menu for the 
corresponding heating circuit (direct heating circuit, mixed heating 
circuit 1, mixed heating circuit 2). 
 
The control circuit is operated with a constant temperature 
specification. The demand value is transmitted to the heat 
generator. The switching program of the respective heating circuit 
and the control modes can be activated. 
The specification of the constant temperature occurs via 
parameter "constant temperature setpoint". 
Upon activation of the function on a mixed heating circuit output, a 
flow sensor is to be set for adjustment of the flow temperature. 
 
5.4.4 "Direct heating circuit" menu (UNMIXED CIRC), Pg. 92 
7.3.3  Fixed-value control  
As with constant control. The demand value is not transferred to 
the heat generator, and the switching time program and control 
modes can be activated.  
 
NOTE
Function
See also
Function