SDC / DHC 
Hydraulic Components 
EN2H-0221GE51 R0808 
169 
7.3.4  Consideration of the room temperature/room influence  
7.3.4.1 Heating 
circuit room connection  
This function determines the enabling of the room sensor in 
conjunction with a wall device/room sensor with the direct heating 
circuit and all parameters affected by the room temperature 
sensing depending on the application. 
 
with the following conditions:  
•  No room sensor connection with installation of the room 
sensor outside the inhabited area (e.g. in unheated rooms like 
basements etc.). 
•  No room sensor connection with multi-family dwellings that 
work with different room temperatures based on different 
assignments and do not offer a reference room. 
•  With room connection switched off, the current room 
temperature is not displayed in the system information. 
•  The flow temperature is corrected purely by weather 
conditions. 
 
for room influence and connected outside sensor:  
•  With the room sensor switched on, the heating circuit is 
controlled based on the weather taking into account the 
current room temperature. The room temperature deviation is 
taken into account based on the room factor parameter 
setting. 
•  If SDW 30 wall devices are connected, the actual room 
temperature is indicated in the basic display instead of the 
heat generator temperature. 
•  When the actual room temperature drops below the current 
setpoint room temperature + 1 K, any active summer switch-
off is disabled, provided automatic operation was not selected. 
 
This setting enables the room temperature-related functions, 
while operation via the wall device is disabled.  
 
Public buildings (government, schools, public facilities, etc.) 
where only the registration of the room temperature is required. 
 
Function
No room sensor 
Room sensor active 
Room sensor active, 
operation disabled 
Application