Desa WMN10 ユーザーズマニュアル

ページ / 60
www.desatech.com
123995-01C
12
Test Pressures Equal To or Less Than 
1/2 PSIG (3.5 kPa)
1.  Close equipment shutoff valve (see Fig-
ure 14).
2.  Pressurize supply piping system by either 
opening  propane/LP  supply  tank  valve 
for propane/LP gas or opening main gas 
valve  located  on  or  near  gas  meter  for 
natural gas, or using compressed air.
3.  Check all joints from gas meter for natu-
ral  or  propane/LP  supply  to  equipment 
shutoff valve (see Figure 15 or 16). Apply 
a noncorrosive leak detection fluid to all 
joints. Bubbles forming show a leak.
4.  Correct all leaks at once.
INSTALLATION
Continued
Figure 14 - Equipment Shutoff Valve
Equipment 
Shutoff Valve
Open
Closed
Propane/LP 
Supply Tank
Control Valve Location
Figure 16 - Checking Gas Joints for 
Propane/LP Gas
Figure 15 - Checking Gas Joints for 
Natural Gas
Control 
Valve 
Location
Gas Meter
Equipment 
Shutoff 
Valve
Equipment Shutoff Valve
CHECKING GAS CONNECTIONS
 WARNING: Test all gas piping 
and  connections,  internal  and 
external to unit, for leaks after 
installing or servicing. Correct 
all leaks at once.
  WARNING:  Never  use  an 
open flame to check for a leak. 
Apply a noncorrosive leak detec-
tion fluid to all joints. Bubbles 
forming show a leak. Correct all 
leaks at once.
  CAUTION:  For  propane/LP 
gas, make sure external regula-
tor has been installed between 
propane/LP supply and heater. 
See guidelines under Connect-
ing to Gas Supply, page 10.
PRESSURE TESTING GAS SUPPLY 
PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG 
(3.5 kPa)
1.  Disconnect  appliance  with  its  appliance 
main gas valve (control valve) and equip-
ment shutoff valve from gas supply piping 
system. Pressures in excess of 1/2 psig 
will damage heater regulator.
2.  Cap off open end of gas pipe where equip-
ment shutoff valve was connected.
3.  Pressurize supply piping system by either 
opening  propane/LP  supply  tank  valve 
for propane/LP gas or opening main gas 
valve  located  on  or  near  gas  meter  for 
natural gas, or using compressed air.
4.  Check all joints of gas supply piping sys-
tem. Apply a noncorrosive leak detection 
fluid to all joints. Bubbles forming show a 
leak.
5.  Correct all leaks at once.
6.  Reconnect heater and equipment shutoff 
valve to gas supply. Check reconnected 
fittings for leaks.