2.  Pressurize  supply  piping  system  by  either 
opening propane/LP supply tank valve for 
propane/LP gas or opening main gas valve 
located on or near gas meter for natural gas 
or using compressed air.
3.  Check all joints from gas meter for natural gas 
(see Figure 17) or propane/LP supply tank for 
propane/LP gas, to equipment shutoff valve 
(see Figure 18). Apply a noncorrosive leak 
detection fluid to all joints. Bubbles forming 
show a leak. 
4.  Correct all leaks at once.
PRESSURE TESTING HEATER GAS 
CONNECTIONS
1.  Open equipment shutoff valve (see Figure 16, 
page 13).
2.  For natural gas open main gas valve located 
on or near gas meter. For propane/LP gas open 
propane/LP supply tank valve.
3.  Make sure control knob of heater is in the OFF 
position.
4.  Check all joints from equipment shutoff valve 
to thermostat gas valve (see Figure 17 or 18). 
Apply a noncorrosive leak detection fluid to 
all joints. Bubbles forming show a leak.
5.  Correct all leaks at once.
6.  Light heater (see Operating Heater, starting 
on page 15). Check all other internal joints for 
leaks.
7.  Turn off heater (see To Turn Off Gas to Appli-
ance, page 16 or 17, depending on your model 
heater).
8.  Replace front panel.
Figure 18 - Checking Gas Joints for 
Propane/LP Gas
Equipment Shutoff Valve
Propane/LP 
Supply Tank
Thermostat Gas Valve
Figure 17 - Checking Gas Joints for 
Natural Gas
Equipment Shutoff Valve
Gas 
Meter
Thermostat Gas Valve