Figure 9 - Clearances for Combustible 
Mantels
Figure 8 - Side Clearances for 
Combustible Mantels
PRE-INSTALLATION PREPARATION
Continued
1
/
2
"
(3.8 cm)
1
/
2
"
(8.9 
cm)
Outer
Surround
Combustible
Material May
Be Used
Perpendicular
Side Wall
1
/
4
"
(13.3 cm)
3
/
4
"
(4.4 cm)
To Fireplace
Opening
10" (25.4 cm)
33°
Safe
Zone
Ref. Mantel.Depth Ref.
Mantel.from.
Top.of.Louver.
Opening
1
16".(40.6.cm)
.A
18".(45.7.cm)
14".(35.6..cm)
.B
16".(40.6.cm)
3
1".(30.5.cm)
.C
14".(35.6.cm)
4
10".(5.4.cm)
.D
1".(30.5.cm)
5
8".(0.3.cm)
.E
10".(5.4.cm)
6
4".(10..cm)
.F
8".(0.3.cm)
7
".(5.1.cm)
.G
6".(15..cm)
C
B
A
D
E
F
G
Top of Louver 
Opening
3
2
1
4
5
6
7
Stud Wall
4" B-Vent
Flue Pipe
2 x 4 Header
at 1" Min.
Clearance
MANTEL CLEARANCES
Figure  8  shows  projected  mantel  depths  at 
various.heights.above.top.of.louver.opening..
Figure 7, page 7, shows minimum allowable 
distances.from.various.mantel.components.in.
relation to both sides of fireplace opening.
  WARNING:  When  finishing 
appliance  do  not  overlap  com-
bustible materials onto the black 
front  face.  Brick,  tile  or  other 
noncombustible materials may be 
applied to the face provided that 
any  fireplace  openings  are  not 
blocked and gaps in the material 
used and the face are sealed with 
a noncombustible caulking.