Desa CB36P ユーザーズマニュアル

ページ / 36
www.desatech.com
117437-01D
10
In.each.case.the.offsets.must.be.supported.
and  firestops  must  be  positioned  wherever 
the vent must pass through a sub-floor, ceil-
ing joist or an attic overhang. The vent pipe 
must.terminate.vertically.into.a.listed.type.vent.
cap  and  extend  a  sufficient  height  through 
an approved roof flashing, roof jack or a roof 
thimble..At. all. points. the. listed. clearances.
must.be.maintained.
Vent.terminations.must.be.located.in.accor-
dance.with.height.and.proximity.rules.of.NFPA 
No. 54
.or.CAN/CSA B149..These.rules.apply.
to.vents.at.1".diameter.or.less.and.require.a.
minimum.height.in.accordance.with.the.roof.
pitch.and.a.minimum.of.8.foot.distance.from.a.
vertical.wall.or.obstruction.(see.Figure.11).
If venting horizontally through a side wall be-
comes necessary, a listed thimble approved 
for.use.with.B-type.vent.must.be.used..Check.
with.your.local.codes.before.venting.through.
a.side.wall.
Some.codes.areas.allow.the.use.of.existing.B-
type.vent.systems.if.the.system.is.at.or.above.
the recommended diameter of the flue.
The flue connection must be made using listed 
B-type. connectors. and. the. existing. system.
must.be.code.inspected.for.damage.and.proper.
installation.
It.is.not.recommended.that.this.appliance.be.
common.vented.with.and.existing.gas.burning.
appliance. However, if it becomes necessary 
to.common.vent.the.appliance..The.venting.
system must be sized and configured in ac-
cordance. with. the. common. venting. guides.
Appendix. G. of. the. current. National  Fuel 
Gas Code NFPA No. 54/ANSI Z223.1
.and.in.
Canada.with.CAN/CSA B149.
Note: Before connecting this appliance to an 
existing  vent  system  or  a  common  venting 
system consult with your local architect plan-
ner, or building official.
VENTING INSTALLATION
Continued
Lowest
Discharge
Opening
Listed
Vent Cap
8 Ft. Min.
Roof Pitch x/12
Listed Clearance
12
x
Listed
Gas
Vent
H (Min)
Height
From Roof
Figure 11 - B-Vent Termination
Roof Pitch
H (Min.)
Flat.to.6/1
1.0.ft.(0.3.m)
6/1.to.7/1
1.5.ft.(0.38.m)
Over.7/1.to.8/1
1.5.ft.(0.46.m)
Over.8/1.to.9/1
.0.ft.(0.61.m)
Over.9/1.to.10/1
.5.ft.(0.76.m)
Over.10/1.to.11/1 3.5.ft.(0.99.m)
Over.11/1.to.1/1 4.0.ft.(1..m)
Over.1/1.to.14/1 5.0.ft.(1.5.m)
Over.14/1.to.16/1 6.0.ft.(1.83.m)
Over.16/1.to.18/1 7.0.ft.(.13.m)
Over.18/1.to.0/1 7.5.ft.(.7.m)
Over.0/1.to.1/1 8.0.ft.(.44.m)
Figure 10 - Typical B-Vent Configuration
Maintain
Listed
Clearance
Maintain
Listed
Clearance
12' Min.
12' Min.
45°
45 
6'
8'
12' Min.
60
45 
Position
Firestop
Position
Firestop
Position
Firestop
Listed
Vent Cap
Listed
Vent Cap
Listed
Vent Cap
Maintain
Listed
Clearance
Maintain 
Listed 
Clearance 
Maintain
Listed
Clearance
Maintain
Listed
Clearance
Support Each
Lateral At
Least Every
6 Feet
Maintain
Listed
Clearance
10'
EXAMPLE 3
EXAMPLE 2
EXAMPLE 1