6. WATER SUPPLY - Required Criteria
9. WIRING THE STEAM HUMIDIFIER
7.   M OUNTING  THE  STEAM  HUMIDIFIER
8. STEAM OPERATION - Required Criteria
A. WATER SUPPLY USING THE SADDLE VALVE
    FURNISHED WITH UNIT.  Important! See page 14.
A.  INSTALLING AND WIRING THE HUMIDISTAT
B. OVERFLOW & DRAIN LINES - Required Criteria
Installation instructions for the saddle valve are printed on the 
plastic bag containing the saddle valve and its components. 
Tap  into  a  1/2”  or  3/4”  domestic  cold  water  line.  Avoid 
connecting to water lines from a Reverse Osmosis system or 
De-ionized water systems. The supply water must read a 
minimum of 25 ppm in order for the Steam unit to reliably 
sense the water. 
NOTE: Never install the saddle valve on the bottom of the 
water pipe. Sediment in the water pipe may clog the saddle 
valve. Flush the line before connecting to the unit. 
tightening the hex compression nut, tighten only enough to 
assure there are no leaks.
NOTE: Saddle valves do not meet plumbing codes in some 
areas. A “T” fitting with a valve may be required to meet code 
or, if low water pressure causes frequent water alerts on the 
steam humidifier. NOTE: Flush the new water line before 
connecting it.
NOTE: The use of City water or Municipal water is preferred. 
Softened water is preferred over untreated well water. Specify 
the Optional WFA-195 disposable water filter for treating 
any water supply that is very high in mineral content.
NOTE:  Use  a  water  hammer  arrester  (WH-100)  if  water 
spikes occur (pipes bang)during fill ups.
When 
A temperature sensor is mounted in the water reservoir of the 
humidifier. As  the  water  temperature  increases  to  about  170 
degrees F, the computer closes a set of blower relay contacts to 
start the system fan. When the water cools to about 140 degrees 
F, the  computer will open the relay contacts to shut off the fan. 
This operational sequence drastically decreases the chances of 
condensation occurring inside the duct-work.
A humidistat, such as the Model #072000 is required to control 
the Steam Humidifier. The humidistat may be installed on the 
wall  in  the  living  space  or  on  the  return  air  duct.  NOTE: 
Continuos fan operation should be initiated if the humidistat is 
installed on the return air duct! Instructions for installation are 
packaged  with  each  humidistat.  Follow  wiring  instructions 
carefully!
DO NOT connect any foreign voltage to the “H” terminals of the 
humidifier! The Humidifier   supplies it’s own control voltage. 
Simply connect the two “H” terminals straight to any dry contact 
humidistat terminals. If you are using a 3rd party Humidistat 
that has powered terminals, you must use an isolating relay 
to operate the Steam Humidifier. Failure to do so will result 
in circuit board failure  and will  void all  warranties.
Schematics  on  the  following  pages  describe  the  suggested 
interlock  wiring  arrangement  for  different  HVAC  systems. 
Interlocking may be performed on systems that provide a 24vac 
NEC Class 2 terminal block for system control.
AIR  PROVING  FEATURE:  The  Steam  Humidifier  has  an 
integrated air proving feature that allows the user to install a sail 
switch  and/or  high  humidity  switch  in  the  duct  and  easily 
achieve fail safe shutdown in the event of fan/blower failure. 
This  feature  prevents  the  Steam  Humidifier  from  operating 
unless adequate airflow is proven thereby avoiding a saturated 
duct condition. WARNING: It is highly recommended to use 
an  airflow  proving  device.  In  particular  Duct-Board 
applications should always use an airflow proving device.  
A factory jumper wire is provided and must be removed when 
connecting  the  sail  switch  or  other  field  supplied  air  flow 
proving device. Leave the jumper in place if you decide not to 
use the airflow proving feature. 
IMPORTANT NOTE: If the Steam Humidifier is removed 
and  disconnected  from  the  system,  the  blower  interlock 
circuit must be restored to it's original configuration. Failure 
to do so may result in loss of blower operation during cooling 
modes!
Use gasket material to seal where the front plate or tank flange 
contacts the duct-work. Place the humidifier reservoir into the 
opening  in  the  duct  and  secure  with  eight  (8)  sheet  metal 
screws. 
NOTE: If the duct-work will not support the unit in a level 
position with the water pan full of water, the duct-work 
must  be  reinforced.  Both  steam  models  weigh 
approximately 9 Lbs. empty and approximately 15 Lbs. 
when full of water.
Because of the high output of this Humidifier, it must not be 
operated  without  the  blower  operating.  The  steam 
humidifier is designed to be "Dominant" over the HVAC 
System Blower. The "System" Blower will be operated by the 
humidifier  when  the  water  tank  temperature  reaches  170 
degrees F. A minimum of 800 cfm @ 800-900 fpm is required for 
proper operation of the steam humidifier. Lower velocities may 
result in excessive condensation inside the duct. See Air Proving 
Feature on the next column! See Variable Speed on Page 7.
The use of an overflow line and drain line is always required.
Use the supplied 1/2” ID high temperature hose. Slip the hose 
over the 1/2” OD “T” drain fitting and use a hose clamp to 
secure. Route the hose to a suitable drain, avoiding kinks, 
traps and sharp objects. DO NOT route the hose above the 
humidifier.  Failure to install all necessary drain lines may 
result in water leaks during normal operating conditions, 
and voids all warranties.
3
B.  FIELD WIRING
IMPORTANT:  Dedicated  fused  circuits  and  outlets  of  the 
proper voltage and current ratings must be provided. Use a 
NEMA 5-20R receptacle for the S2000 and a NEMA 6-15R 
receptacle for the S2020. All wiring must conform to local and 
national codes. Failure to do so will void all warranties. 
DO NOT cut off the grounded plug and/or hard wire this unit to 
line voltage!  DO NOT use extension cords to operate this unit! 
Doing so will void all warranties.
When routing the S2000 drain hose into a condensate pump, 
be sure to cut the end of the hose at a sharp angle to prevent 
the hose from bottoming out in the pan. It could result in 
poor draining or no draining at all. Failure to do so may 
result in water backing up into the S2000 reservoir and 
eventual overflow. See Figure 5.
CORRECT
INCORRECT
X
CONDENSATE
PUMP
DRAIN
HOSE
FIG. 5