If it is necessary to adjust the dip switch, ensure that no other dip switches are 
changed. Unauthorized adjustments can cause property damage, personal 
injury, scalding, or death.
Rinnai America
FF  Models
I N S TA L L E R ’ S  I N S TA L L AT I O N  I N S T R U C T I O N S
Venting
Air  Intake  and  Exhaust  Vent  Pipe  Length
Determine  the  number  of  elbows  in  the  vent  system. The  corresponding  number  from  the  table 
indicates  the  maximum  length  of  vent  pipe.
For  high  altitude  installations  contact  Rinnai  at  1-800-621-9419.
Table  1  Maximum  Vent  Length  (feet)
 
Two 45  elbows are considered equivalent to one 90° elbow.
Include termination elbows when using this table.
(1) If the length is less than 22' then move dip switch no. 1 (SW 1) to ON
(2) If the length is less than 16' then move dip switch no. 1 (SW 1) to ON
(3) If the length is less than 10' then move dip switch no. 1 (SW 1) to ON
Number of 90° Elbows
3
23
4
17
5
11
6
5
2
29 (3)
1
35 (2)
0
41 (1)
 
Intake/Exhaust  Guidelines
•  This water heater is a direct vent water heater and therefore is certified and listed with the 
vent  system. The  only  vent/air  intake  system  listed  for  use  with  this  appliance  is  the  Rinnai  / 
Ubbink  vent  system  or  the  Heat-Fab  Saf-T  Vent  SC  system.
•  Minimum wall thickness is 4”. Maximum wall thickness is 20”.
•  Do not combine vent components from different manufacturers.
•  The vent system must vent directly to the outside of the building and use outside air for 
combustion.
•  Before installation, inspect each vent component for damage and correct seal placement. Do 
not  attempt  to  fix  or  install  any  damaged  vent  components.
•  Every vent connection must be accessible for inspection, cleaning, and replacement.
•  Avoid dips or sags in horizontal vent runs by installing supports per the vent manufacturers’ 
instructions.
•  Support horizontal air intake runs every four feet and all vertical air intake runs every six 
feet  or  in  accordance  with  local  codes.
•  Venting should be as direct as possible with a minimum number of pipe fittings.
•  Vent diameter must not be reduced.
•  Do not connect the venting system with an existing vent or chimney.
•  Do not common vent with the vent pipe of any other water heater or appliance.
•  Vent connections must be firmly pressed together so that the gaskets form an air tight seal.
•  Refer to the vent pipe manufacturers’ instructions for component assembly instructions.
•  The first vent component to the appliance must be an appliance adapter. This will prevent 
additional  components  from  being  installed  backwards.