Gas Piping Sizing Chart
Capacity Table for Natural Gas
cubic feet / hour
(table assumes .3 inch pressure drop, specific gravity of .60)
Nominal  
 
 
 
Length of Pipe in Feet
Iron Pipe
Size
Inches
 
10 
20 
30 
40 
50 
60 
70 
80 
90  100 
125  150  175  200
3/4 
278  190  152  130 
115  105 
96 
90 
84 
79 
72 
64 
59    55
520  350  285  245  215  195  180  170  160  150 
130  120 
110  100
1-1/4  1050  730  590  500  440  400  370  350  320  305 
275  250  225  210
1-1/2  1600  1100  890  760  670  610  560  530  490  460 
410  380  350  320
After  determining  the  length  of  pipe  required  select  the  pipe  size  that  will  supply  the 
cubic  feet  per  hour  of  gas  required  for  the  input  rating  of  the  Rinnai  Water  Heaters.
The  formula  for  figuring  the  cubic  feet  per  hour  required  is:
 
 Gas  Input  of  Rinnai  water  heater  (BTU/HR) 
 
CFH  =
 
 
Heating  Value  of  Gas(BTU/FT
3
)
*Gas  input  requirement  is  on  the  water  heater  data  plate 
*The  heating  value  of  the  gas  can  be  obtained  from  the  local  Natural  Gas  Utility 
Capacity Table  for  LP  Gas 
BTUH  of  undiluted  liquified  petroleum  gases 
(table  assumes  11  inches  of  water  column  pressure  at  the  inlet,  .5  inch  drop) 
Nominal  
 
 
 
Length of Pipe in Feet
Iron Pipe
Size
Inches
 
10 
20 
30 
40 
50 
60 
70 
80 
90 
100  125  150
1/2 
275    189  152    129
3/4 
567  393  315  267  237  217  196  185    173    162    146
1071  732  590  504  448  409  378  346 
322 
307  275  252
1-1/4  2205  1496  1212  1039  913  834  771  724 
677 
630  567  511