All installations and services must be performed by qualified service personnel. 
 
 
#8 x ½ TEK screws for  
mounting 2 x 4 J-box 
300208 
 
#10-32 x ½ green ground screw 
300109 
 
#10-32 hex nut 
300110 
 
3/16” dia. star washer 
300270 
 
Grounding instructions 
MG-966 
 
Wire nut 
300132 
 
3” stainless steel hose clamp 
300276 
 
J-box wire bushing  
350016 
 
Drain hose grommet 
350446 
 
Spring clamp, 11/16” 
300299 
 
Installation notice 
MG-987 
 
PVC tee assembly, 2 x 3” dia. 
320817 
 
PVC tee assembly, 2” dia. 
320819 
 
Pipe 2” dia. PVC 15” 
14401 
 
Bracket 
14406 
 
Reducer 2” x 3” PVC 
320067 
 
CPVC XPVC adapter 
320833 
 
Gas Conversion Kit 
AOPS7679/7664 
 
 
III. GENERAL INSTALLATION 
This furnace is equipped with orifices size for operation with natural gas.  For conversion to Propane Gas see 
instruction in Gas Conversion Section of this manual. 
 
These Category Type IV furnaces are shipped completely assembled and wired (internally). See the Dealer 
Receiving and Freight Claim Procedure  Section of the price guide for parts shortage or damage. The furnace and 
duct system must be adjusted to obtain a temperature rise of 55°F to 85°F (35°F to 65°F CHB1-75) through the 
furnace after installation. (See rating label located on side panel inside the furnace vestibule). The installation must 
conform with local codes, or in the absence of local codes, with the National Fuel Gas Codes (ANSI Z223.1 or latest 
edition) and with these instructions. 
 
: This furnace is not to be used for temporary heating of buildings or structures under construction. 
 
Many of the chemicals used during construction, when burned, form acid bearing condensate that can substantially 
reduce the life of the heat exchanger. 
 
It is recommended that a commercially available CO alarm be installed in conjunction with any fossil fuel burning 
appliance.  The CO alarm shall be installed according to the alarm manufacturer’s installation instructions and be 
listed in accordance with the latest edition of the UL Standard for Single and Multiple Station Carbon Monoxide 
Alarms, UL 2034, or the CSA International Standard, Residential Carbon Monoxide Alarming Devises, CSA 6.19. 
 
A. CODES AND CLEARANCES 
 
The following items must be considered when choosing the size and location of the furnace.
 
 
1.  All local codes and/or regulations take precedence over the instructions in this manual and should be followed 
accordingly. In the absence of local codes, installation must conform with these instructions, regulations of the 
National Fire Protection Association, provisions of National Electrical Code (ANSI/NFPA70 or latest edition), 
and the National Fuel Gas Code (ANSI Z223.1 or latest edition).