All installations and services must be performed by qualified service personnel. 
 
4.  This furnace must be connected to a drain in accordance with these instructions. If it is not practical to connect 
the unit to a drain, a condensate pump must be used and can be ordered as an
 
accessory, part number 350225. If 
an acid neutralizer kit is required by local code or the customer, it is available under part number 320095. 
 
 
B1.  CDB1 HORIZONTAL APPLICATION 
 
The CDB1-50, 75, 100, and 125 furnaces may be installed in a horizontal position by placing the furnace on the left 
or right side (as viewed from the front in the upright position).  
 
For left or right horizontal applications of the CDB1 series units, the rollout switch located on the burner box must 
be moved to the pre-punched mounting holes on the side of the burner box. Screws are provided in pre-punched 
holes at the required limit location. Remove these screws and use them to mount the limit to new location. Utilize 
previously removed limit mounting screws to fill voided holes at previous limit location (See Figure 1).  
 
For a right side horizontal application of the CDB1 series units, the hose from the single tap pressure switch (top 
switch) is already connected correctly (See Figure 1).  
 
For a left side horizontal application of the CDB1 series units, the hose from the single tap pressure switch (bottom 
switch) must be moved to the lower front tap on the face of the collector box. Use the black cap removed from this 
tap to plug the original pressure switch tap.  
NOTE: The hose, when moved, must be shortened (cut) to ensure that no excess hose exists to cause a sag, loop, or 
"water trap". 
 
For a right side horizontal application of the CDB1 series units, the auxiliary limit switch located on the right side of 
the house air blower must be moved to the bracket on the opposite (left) side of the blower (See Figure 1). 
 
NOTE: When the CDB1 is installed as horizontal unit, it is imperative that the auxiliary limit switch and bracket be 
located on the upper side of the house air blower; the burner rollout switch located on the burner box be relocated to 
the side of the burner box; and that the hose from the single tap pressure switch be connected to the lower tap on the 
front of the collector box (See Figure 1).