Thermo Products 100n ユーザーズマニュアル

ページ / 67
All installations and services must be performed by qualified service personnel. 
CDX3 SERIES 
 
MODEL NO. 
CDX3-75 
CDX3-100 
CDX3-125 
BTU/HR INPUT (High fire / Low fire) 
75,000 / 56,250
100,000 / 
75,000 
125,000 / 
93,750 
BTU/HR OUTPUT (High fire / Low fire) 
71,000 / 52,000
94,000 / 69,000 
116,000 / 
87,000 
 
 
 
 
HEIGHT OF CASING 
46-1/4” 46-1/4”  46-1/4” 
WIDTH OF CASING 
17” 21”  24” 
DEPTH OF CASING 
27-1/2” 27-1/2”  27-1/2” 
WARM AIR OUTLET 
15 x 18 
19 x 18 
22 x 18 
RETURN AIR INLET 
15 x 22 
19 x 22 
22 x 22 
 
 
 
 
DIA. OF FLUE 
2” 3”  3” 
DIA. OF COMBUSTION 
AIR INTAKE 
2” 3”  3” 
 
 
 
 
CFM from .2” & .5” w.c.  
EXTERNAL STATIC PRESSURE 
COOLING COOLING  COOLING 
 
 
 
 
       @COOLING TAP A 
1000 1200  1400 
       @COOLING TAP B 
800 1000 1200 
       @COOLING TAP C 
1200 1400  1600 
       @COOLING TAP D 
1400 1600  2000 
 
 
 
 
 
HEATING HEATING  HEATING 
      @HEATING TAP C (High fire / Low 
fire) 
1012 / 826 
1340 / 1094 
1673 / 1366 
 
 
 
 
TEMPERATURE RISE 
65 / 60 
65 / 60 
65 / 60 
BLOWER MOTOR HP 
.5 .75  1 
 
 
 
 
POWER CHOKES 
- 2.65Mh 
2.1Mh 
LARGEST RECOMMEDED 
AIR CONDITIONER 
3.5 Ton 
4 Ton 
5 Ton 
SIZE OF FILTERS 
21-3/4” x 14”(2) 
21-3/4” x 14”(2) 
21-3/4” x 14”(2) 
NOTES: 
1.  BTU output based on annual fuel utilization efficiency rated by manufacturer. 
2.  On all outlet and inlet dimensions, the first dimension is width. 
3.  To permit largest recommended air conditioning (at .5 static pressure), selection of the highest motor 
speed is required. 
4.  Electrical characteristics at 115 volts, 60 Hz., 1 phase (less than 15 amps. for all models). 