350-2100 cfm Dryers 
Chapter 6: Maintenance 
51 of 58 
 
 
LEVEL 2 
In this level, parameters such as the type of 
temperature sensor connected to the 
regeneration monitor, Fahrenheit/centigrade 
display, and display refresh cycle can be set. 
 moves from one parameter to the next. 
When the desired parameter appears on the 
LED display, press 
 to select that 
parameter for programming. The current 
value of the parameter is then displayed on 
the LED display. Use 
 and 
 to change 
the setting. When you are satisfied with the new setting, press 
 to save the new setting to memory
Sensor Input Type
 
  
The regeneration monitor is factory equipped with and configured to use a type K thermocouple. Type 
R, S, J, L, T, U, E, and 1OO 
W
 RTD’s can also be used. The factory setting is 
Press 
 after 
 appears on the LED display. Use 
 to scroll through the available sensor 
types. Then press 
 to save the new setting to memory. 
 
Scale Indication
 
 
The regeneration monitor can display the regeneration bleed air temperature in either Fahrenheit (°F, 
the factory default) or Celsius (°C). The control is factory set to the scale indicated on the dryer at the 
time of purchase.   
Press 
 after 
 appears on the LED display. Use 
 to toggle between the two choices. 
Then press 
 to save the new setting to memory. 
Display Refresh Cycle
  
  
The regeneration monitor’s display refresh speed can be set separately from the sampling speed.  
Press 
 after 
 appears on the LED display. Use 
 to toggle between the two choices: 
 (500 ms) or  
  (2 seconds). Then press 
 to save the new setting to memory. The 
factory setting is 
 
Note:  Even if the display refresh speed is set to two seconds, the sampling times for the 
setpoints still remains at 500 milliseconds. 
 
Sensor Input Type
Scale Indication °C or °F
Display Refresh Cycle