3.  Activate the enter key (switch 3) to display the sub menu: hour’, ‘minute’, ‘seconds’.  
 
4.  Activate the up arrow key (switch 1) to change the current hour/minute/second settings, then use switch 2 to 
cycle across  ‘hour’, ‘minute’, ‘seconds’ values and ‘OK’.  
 
5.  After desired settings are made, navigate to ‘OK’ and activate the enter key (switch 3) to confirm. To exit main 
menu, select “Exit” at each menu stage (sub menu and main menu). 
 
4.3.2 View Event Log 
The Millennium II Transmitter has the ability to store up to 980 events. Events can be viewed by navigating through 
this menu option. The most recent events are shown first.  
 
1.  Enter the main menu by activating any key to get the “enter main menu” prompt, then activate switch 1 to 
select “yes”. 
 
2.  Navigate through the main menu using switch1 or switch 2 until “View Event Log?” is displayed.  
 
3.  Activate the enter key (switch 3) to display the sub menu. The most recent event will be displayed.  
 
4.  Select the up arrow key (switch 1) and the down arrow key (switch 2) to toggle through all past events.  
 
6.  After viewing, select “Exit” at each menu stage (sub menu and main menu). 
 
The on-screen Events Format/host includes:  
 
• Channel Number: CH1CH2, or transmitter: ML2.  Events that occurred under these formats will be logged.  
 
• Event Types: There are a total of 11 events that are stored and displayed. See Table 5 for a list of the events, and 
how they are displayed on the Millennium II screen.  
 
• Date and Time: Each event is date and time stamped. 
   
                   
                  
Table 5: Event Types 
Event Types 
Display on Screen 
Events Format /host 
Power up or Reset 
Power UP / RST 
ML2 
Communication Fault 
Communication Err 
CH1 or CH2 
High Level Alarm 
High Alarm 
CH1 or CH2 
Low Level Alarm 
Low Alarm 
CH1 or CH2 
Calibration Completed 
Cal Complete 
CH1 or CH2 
Calibration Zero Failed 
Cal Zero fail 
CH1 or CH2 
Calibration Span Fail 
Cal Span Fail 
CH1 or CH2 
Calibration Aborted 
Cal Abort 
CH1 or CH2 
Sensor Fail 
Sensor Fail 
CH1 or CH2 
Channel Enabled 
Enabled 
CH1 or CH2 
Channel Disabled 
Disabled 
CH1 or CH2