Radiance Direct Vent/Natural Vent Gas Heater 
20004188
Vertical (Through the Roof) 
Vent Assembly
Note that all vertically terminated installations 
must, where specified, use the restrictor plate to 
comply with Vertical Termination Window (Page 
7, Figure 8), 
included in the hardware bag. The plate 
must be installed within the firebox inner flue collar to 
insure a proper air/fuel ratio is maintained in an appli-
ance vented through the roof.
ST653
install snorkel
4/20/01   djt
RADIANCE
Waterproof Seal 
Around Pipe
Firestop
Window Well
Drain
4” Clearance
Snorkel 
Termination 
Cap
Wall Screws 
and Anchors
ST653
Gravel
Fig. 31  Snorkel kit installation.
Vent Termination Below Grade
Install Snorkel Kit #7FSDVSKS when it is not possible 
to meet the required vent termination clearances of 12” 
(305mm) above grade level. The snorkel kit will allow 
installation depth of down to 7” (178mm) below grade 
level. The seven inches is measured from the center of 
the horizontal vent pipe as it penetrates the wall. If the 
venting system is installed below grade, a window 
well must be installed with adequate and proper 
drainage.
 (Fig. 31)
NOTE: Be sure to maintain side wall clearances and 
vent run restrictions. Refer to Page 6, Figures 3, 4, 5, 6.
1.  Establish the vent hole through the wall.
2.  Remove soil to a depth of approximately 16” (406 mm) 
below the base of the snorkel. Install a window well 
(not supplied). Refill the hole with 12” (305mm) of 
coarse gravel and maintain a clearance of at least 4” 
(102 mm) below the snorkel. (Fig. 31)
3.  Install the vent system as described on pages 15-18.
4.  Be sure to make a watertight joint around the vent 
pipe joint at the inside and outside wall joints.
5.  Apply high temperature sealant around the inner 
and outer snorkel collars. Join the pipes and fasten 
the snorkel termination to the wall with the screws 
provided.
6.  Level the soil to maintain a 4” clearance below the 
snorkel.
  If the foundation is recessed, use extension brack-
ets (not supplied) to fasten the lower portion of the 
snorkel. Fasten the brackets to the wall first, and 
then fasten to the snorkel with self-tapping #8 x 1/2” 
sheet metal screws. Extend the vent pipes out as far 
as the protruding wall face. (Fig. 30)
ST219
snorkel detail
12/6/99   djt
Recessed Wall
Sheet Metal 
Screws and 
Bracket
Wall Screws 
and Anchors
Waterproof Seal 
Around Pipe
ST219
Fig. 30  Use extension brackets to mount snorkel against 
recessed wall.
Firestop
Finishing 
Collar
7” Pipe
Wall Plate
ST217
install wall terminal
12/6/99   djt
Seal Both Termi-
nal Ends
Caulk Plate Joint with 
Weatherproof Sealant
ST217
Fig. 29  Install the vent terminal.
11. For CFM only: Install Charcoal Gray Pipe Rings 
(#7FSDRG) or Polished Brass Pipe Rings (#7FSDRP) 
at pipe joints, if desired.