Honeywell 700 ユーザーズマニュアル

ページ / 40
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD
66-2069—02
12
INCREASE, DECREASE and STORE buttons (range 
of 00 to 29).
• LOAD FACTORY DEFAULTS button:
— Used to restore all settings to the factory default 
values
  
INCREASE button:
— Used to increase parameter value when in 
programming mode
• RATIO (%) RELAY OFF/RELAY ON button:
— Used along with the INCREASE, DECREASE and 
STORE buttons to set the RELAY OFF setpoint at a 
percentage of the RELAY ON setpoint. Adjustable 
from 20% to 80%.
• STORE  button:
— Stores new parameter values during programming
— After making changes “--” will be displayed indicating 
the new values are accepted and stored
  
DECREASE button:
— Used to decrease parameter value when in 
programming mode
• BNR-ON SEQ START/END button:
— Used to initiate and proceed through the automatic 
parameter setup sequence, which includes the RELAY 
ON, RATIO (%) and GAIN settings (the FFRT, mA 
output and communication address must be set 
manually)
• BNR-OFF SEQ START/END button:
— Used during the automatic parameter setup sequence
• ACCEPT RATIO/SET GAIN button:
— Allows user to set the viewing head gain in conjunction 
with the INCREASE, DECREASE and STORE buttons
— Used in conjunction with the BNR-ON SEQ START/
END and BNR-OFF SEQ START/END buttons during 
the automatic setup process
• FFRT 1/2/3 SEC OPTION button:
— Used to set the FFRT timing along with the 
INCREASE, DECREASE and STORE buttons
• 0-20MA 4-20MA OPTION button:
— Used in conjunction with the INCREASE, DECREASE 
and STORE buttons to select the proportional mA 
output for the flame signal
• RESET rE button:
— Resets a lockout condition
— Also used to exit a menu while programming
— Used to set the Modbus address along with the 
INCREASE, DECREASE and STORE buttons
Manual Setup of Setpoints
The keypad of the signal processor is used to set the IR/UV 
GAIN, RELAY ON, RATIO % (Relay Off), FFRT and mA output 
option setpoints. The following section describes this process. 
Setting the Viewing Head Gain
The gain of the IR and UV viewing heads can be adjusted. In 
addition to the information in this section, refer to Fig. 26. At 
power-up, the 700 signal processors display codes to tell the 
operator what type of viewing head and what gain is being 
used. Default values are “r5” for the IR viewing head and “u5” 
for the UV viewing head. The “r” or “u” denote IR or UV 
viewing heads, respectively, while the numeric digit indicates 
the current gain setting. The gain can be adjusted from 1 to 9 
with a gain of 5 being the factory default gain. 
To change the gain, press and hold the SET GAIN button for 
two seconds until the current value is displayed. Use the 
INCREASE and DECREASE buttons to change the setting as 
appropriate while the value is displayed. To store the new 
setting, press the STORE button until “- -” is shown, indicating 
the value has been accepted.
If no activity occurs for a period of four seconds while the 
value is displayed, the display will return to the operation 
mode without saving the new setpoint.
To exit the menu at any time without saving changes, simply 
press the RESET/rE button.
The gain is live; changes are effective immediately, but if the 
displayed gain value is not stored (by pressing STORE), and 
no other buttons are pressed, the processor returns to the 
previous setting after four seconds.
Relay On Setpoint
The two numeric digits on the Model 700 signal processor 
normally display the incoming count during operation; that is, 
the number of pulses that arrive between self-check pulses. 
This count ranges from 00 to 29.
Refer to Fig. 22 for a flowchart of setting the Relay On 
setpoint. Press and hold the RELAY ON SETPOINT key for 
two seconds to access this setpoint. The RELAY ON SET 
POINT value will be displayed. If no further keys are pressed, 
this display will disappear in four seconds and the incoming 
count will again be displayed. If the RESET key is pressed, 
the display will return immediately to displaying the incoming 
count.
While the RELAY ON SET POINT is displayed, you may 
increase or decrease the setting by using the INCREASE and 
DECREASE arrow keys. To store the new setting, press the 
STORE button until “- -” is shown, indicating the value has 
been accepted.
To exit the menu at any time without saving changes, simply 
press the RESET/rE button or wait 4 seconds until the display 
reverts to the incoming count value. To extend the display 
time, press the RELAY ON SETPOINT button again; the 
display will time out for four seconds after the key is released if 
no other buttons are pressed.
The displayed value of the RELAY ON SET POINT is live; that 
is, if the relay is off and the adjusted value falls below the 
current flame signal count, the relay will turn on immediately 
(FFRT settings are ignored). This immediate response can be 
seen if the count is low and the RELAY ON SET POINT is set 
above it; if the RELAY ON SET POINT is then adjusted down 
to the count level, the FLAME ON relay will be energized. 
Ratio (%) Relay Off/Relay On Setpoint
For a flowchart of this setpoint process, refer to Fig. 23. The 
key labeled RATIO (%) RELAY OFF/RELAY ON is used to set 
the RELAY OFF SET POINT at a percentage of the RELAY 
ON SET POINT. This percentage is adjustable from 20% to 
80%. For example, if the RELAY ON SET POINT is set to 16 
and the RATIO (%) is set to 50% (the factory default values) 
the relay will energize if the displayed count goes to 16 or 
higher and de-energize when the count drops to 08 or less for 
one to three seconds, depending on the FFRT (Flame Failure 
Response Time) setting. The adjustment of the RATIO setting