Honeywell 700 ユーザーズマニュアル

ページ / 40
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD
13
66-2069—02
is live. Adjustments will cause the Flame Relay to de-energize 
immediately, ignoring FFRT settings.
To access this setpoint, press and hold the ACCEPT RATIO/
SET GAIN button for 2 seconds until the current value is 
displayed. While the value is displayed, adjustments may be 
made via the INCREASE or DECREASE arrow buttons. To 
store the new setting, press the STORE button until “- -” is 
shown, indicating the value has been accepted.
If no activity occurs for a period of four seconds while the 
value is displayed, the RATIO display will disappear and the 
old ratio setpoint will take effect.
To exit the menu at any time without saving changes, simply 
press the RESET/rE button.
Setting FFRT (Flame Failure Response 
Time)
To access the FFRT setpoint, press and hold the FFRT 1/2/3 
SEC OPTION button for 2 seconds until the current value is 
displayed. Refer to Fig. 24 for the setup flowchart. The FFRT 
can be set at 1, 2 or 3 seconds. While the value is displayed, 
adjustments may be made via the INCREASE or DECREASE 
arrow buttons. To store the new setting, press the STORE 
button until “- -” is shown, indicating the value has been 
accepted.
The FFRT changes are not live; they take effect only if the 
STORE button is pressed. FFRT values do not relate to the 
RELAY ON SETPOINT and RATIO (%)/RELAY OFF values. 
Therefore, during automatic setup, if the AUTO SET LED is 
on, confirmation is not needed to change the FFRT setting.
If no activity occurs for a period of four seconds while the 
value is displayed, the FFRT display will disappear and the old 
setpoint will take effect.
To exit the menu at any time without saving changes, simply 
press the RESET/rE button.
0/4-20mA Output Option
An analog output current is provided for operating a remote 
meter or other instrumentation. The load resistance should 
not exceed 360 Ohms for the Model 700 signal processors. 
The resistance can be chosen to give the desired voltage 
swing. For example, if 2V is desired for a 20 mA output, a 100 
Ohm resistor would be used. Fig. 25 contains a flowchart for 
the mA output setup.
The analog current output selections are 0 to 20 milliamps, or 
from 4 to 20 milliamps. Selection of the applicable range is 
made by pressing and holding the 0-20 MA/4-20 MA OPTION 
button until the current value is shown. 02 denotes the 0-
20mA selection while 42 denotes the 4-20mA selection (the 
default value). While the value is displayed, it may be changed 
via the INCREASE or DECREASE arrow buttons. To store the 
new setting, press the STORE button until “- -” is shown, 
indicating the value has been accepted.
Confirmation is not requested if the 0-20/4-20 setting is 
changed when AUTOSET LED is on
The 0/4-20mA output option is live; the operative range 
changes as soon as the displayed selection is changed. 
However, the value must still be saved via the STORE button 
in order to be saved in the signal processor's EEPROM.
To exit the menu at any time without saving changes, simply 
press the RESET/rE button or wait four seconds.
The analog current output is scaled according to the RELAY 
ON setting. It is scaled so that, if the counts coming in are at a 
count rate equal to the RELAY ON setting, the current output 
is approximately 13 MA when the range selected is 0-20 MA, 
and about 14.6 MA when the range selected is 4-20 MA.
Note that the actual maximum level for the current output is 
19.8 MA.
Automatic Setup of Setpoints
With this feature, the Model 700 signal processors set the 
RELAY ON SET POINT, the RATIO % (Relay Off), and the UV/
IR GAIN automatically. Calculations for these settings are 
carried out in the signal processor as the operator takes the 
system through BURNER ON and BURNER OFF sequences. 
Fig. 19, 20 and 21 flowchart the automatic setup sequence.
The FFRT (flame failure response time) and the 0/4-20mA 
output option must be manually setup after the automatic 
setup process is complete. Refer to the Manual Setup of 
Setpoints section and Fig. 24 and 25. for details on setting 
these 2 parameters.
Before starting the automatic setup sequence, adjust the 
RELAY ON SET POINT to get the FLAME ON relay to 
energize.
Press BNR-ON SEQ START/END key for two seconds. If the 
FLAME ON relay is de-energized, the display will show “bo” 
(burner off); press RESET to clear this. If the FLAME ON relay 
is energized, the ON SEQ LED will start flashing slowly and 
the numeric display will start counting down from 59 while the 
processor takes data at one reading per second. The FLAME 
ON relay will remain energized if the flame is present, 
according to the current settings, until valid new values are 
obtained. To end the data sampling, press the same button, 
BNR-ON SEQ START/END, again, but ensure that an 
adequate number of data samples has been taken. At least 30 
seconds of BNR-ON data sampling is recommended; ten 
seconds is a minimum. The software will not respond to a 
second press of the button for 10 seconds. RESET may also 
be pressed while the data sampling is occurring; the data 
sampling process will be aborted and the old values will 
remain in effect.
After BNR-ON data sampling is complete, the OFF SEQ LED 
flashes. Turn off the burner and immediately press the BNR-
OFF SEQ START/END key (a two-second press is not 
required). The displayed timer then counts down from 29. This 
process may be interrupted, but at least 15 seconds of BNR-
OFF data sampling is recommended. The data sampling 
process can be aborted by pressing RESET, in which case the 
data for both BNR-ON and BNR-OFF will be discarded and the 
previous values will remain in effect.
If  the data is good, that is, the computed ratio is 71% or less 
when BNR-OFF data sampling is complete, the display shows 
the ratio in percentage for one second, followed by “- -”  to indicate 
a successful setup.  The signal processor then turns  on  the 
AUTO SET LED to verify that the values stored internally were 
derived from the BNR-ON/BNR- OFF data sampling sequence.
If the data received is marginal, with the computed ratio ranging 
from 72% to 80%, the display alternates be- tween “AC” and