Friedrich SS15N30* ユーザーズマニュアル

ページ / 95
38
 3.  Install a process tube to sealed system. 
4.  Make necessary repairs to system. 
 
5.  Evacuate system to 200 microns or less.  
 
6.  Weigh in refrigerant with the property quantity of R-410A 
     refrigerant. 
 
7.  Start unit, and verify performance. 
8.  Crimp the process tube and solder the end shut.  
Proper safety procedures must be followed, 
and proper protective clothing must be worn 
when working with a torch.
Failure to follow these procedures could 
result in moderate or serious injury.
Proper safety procedures must be followed, 
and proper protective clothing must be worn 
when working with liquid refrigerant.
Failure to follow these procedures could 
result in minor to moderate injury.
WARNING
CAUTION
BURN HAZARD 
FREEZE HAZARD 
Proper safety procedures must be followed, 
and proper protective clothing must be worn 
when working with a torch.
Failure to follow these procedures could 
result in moderate or serious injury.
WARNING
BURN HAZARD 
Method Of Charging / Repairs 
The acceptable method for charging the sealed system is the  
Weighed in Charge Method. The weighed in charge method  is 
applicable to all units. It is the preferred method to use, as  it is 
the most accurate. 
The  weighed  in  method  should  always  be  used  whenever  
a  charge  is  removed  from  a  unit  such  as  for  a  leak  repair, 
compressor  replacement,  or  when  there  is  no  refrigerant  
charge left in the unit. To charge by this method, requires the 
following steps:
1. Install a piercing valve to remove refrigerant from the 
sealedsystem. (Piercing valve must be removed from  the 
system before recharging.) 
2.  Recover Refrigerant in accordance with EPA regulations.