Friedrich SS15N30* ユーザーズマニュアル

ページ / 95
48
1.
2.
3.
4.
5.
ELECTRIC SHOCK HAZARD 
WARNING
Turn off electric power before service or 
installation.
Failure to do so may result in personal injury, 
or death.
Sealed Refrigeration System contains refrigerant 
and oil under high pressure.
Proper safety procedures must be followed, 
and proper protective clothing must be worn 
when working with refrigerants.
Failure  to  follow  these  procedures  could 
result in serious injury or death. 
WARNING
HIGH PRESSURE HAZARD 
The use of nitrogen requires a pressure
regulator. Follow all safety procedures and 
wear protective safety clothing etc. 
Failure to follow proper safety procedures 
result in serious injury or death. 
WARNING
EXPLOSION HAZARD 
Recover all refrigerant and oil from the system.  
 
Remove compressor, capillary tube and filter drier  
from the system.  
 
Flush evaporator condenser and all connecting 
tubing with dry nitrogen or equivalent. Use approved 
flushing agent to remove all contamination from 
system. Inspect suction and discharge line for 
carbon deposits. Remove and clean if necessary. 
Ensure all acid is neutralized. 
 
Reassemble the system, including new drier strainer 
and capillary tube. 
Proceed with step 8-10 on previous page. 
SPECIAL PROCEDURE IN THE CASE OF MOTOR 
COMPRESSOR BURNOUT
Basically, troubleshooting and servicing rotary compres-
sors is the same as on the reciprocating compressor with 
only one main exception:
NEVER, under any circumstances, liquid charge a rotary-
compressor through the 
LOW side. Doing so would cause 
permanent damage to the new compressor. Use a charging
adapter.
ROTARY AND SCROLL COMPRESSOR SPECIAL 
TROUBLESHOOTING  AND SERVICE