SEQUENCE OF OPERATION 
(CONTINUED)
condition be detected, the compressor and condenser fan 
will be switched off for a minimum of three minutes and until 
the freeze condition is satisfied. During this time the indoor 
fan will continue to run to aid in the defrost process.
AJ4004 CONTROL BOARD: There are two sets of jumper 
pins  on  the  control  board  that  are  factory  set  so  there 
should no need to set them later on in the field. The first 
is a set of three pins labeled “HP” for selection of either a 
“Straight Cool” or “Heat Pump” unit. For “Straight Cool” the 
center pin and outer most pin (usually on the top) are to be 
jumped together. For Heat Pump units the center pin and 
the pin closest to the relay are to be jumped together (see 
Firure #1).
The second is a set of two pins labeled “TEST”. When these 
two pins are jumped together, all timers are eliminated (i.e. 
anti-short, purge, ect.). This is mainly used for production 
line testing however it may also be useful for field-testing 
as well. The units are shipped with the “TEST” jumper on 
only one of the pins. Please, do not leave a unit with the 
test jumper in the test mode (see Firure #2).
HEAT PUMP 
      
STRAIGHT COOL
STRAIGHT COOL/HEAT PUMP JUMER
Figure #1
TEST JUMPER POSITION 
FOR NORMAL OPERATION
Figure #2
The LED Blink codes are as listed in below.
1 Blink Normal Operation
2 Blinks Compressor Lockout (ASCT)
3 Blinks Outdoor freeze condition
4 Blinks Indoor freeze condition
5 Blinks Simultaneous W & Y Call
Important sensor resistances are as follows.
77 °F - 10K ohms
50 °F - 19.9K ohms
35 °F - 30K ohms
30 °F - 34.4K ohms
!  
!  
temperature  below  the  room  temperature. The  heating 
mode will cease and the indoor fan will remain on for an 
additional sixty seconds.
NOTE: The start of the compressor will not take place until 
the anti-short/random start time period has elapsed.
HEAT PUMP (Emergency Heat)
WARNING 
Before accessing the control compartment, disconnect 
power  to  the  unit.  Failure  to  do  so  could  result  in 
serious injury or electrical shock.
Should the heat pump system fail, it is possible to force the 
control board into electric heat mode. This is a temporary 
solution  until  the  heat  pump  system  can  be  repaired. 
Locate the circuit board in the control section of the unit. 
Locate the terminals where the outdoor sensor connects 
to the circuit board. Using a small needle nose type pliers, 
disconnect one side of the sensor from the circuit board. 
This will appear to the circuit board as an outdoor coil freeze 
condition there-by energizing the electric resistance heater 
on the call for heat.
HEAT PUMP (Thermostatic Drain Pan Valve): Heat pump 
units are equipped with a thermostatic drain valve that will 
open  when  outdoor  temperatures  fall  below  50°F. This 
keeps the base pan free of condensate water where it may 
otherwise freeze during colder outdoor temperatures. As 
part of its normal operation, the unit will produce condensate 
and collect it in the base pan of the unit. There it will be 
picked up by the condenser fan slinger ring and deposited 
onto the condenser coil. During the cooling season, this 
improves  the  unit’s  efficiency  by  maintaining  adequate 
refrigeration system pressures.
ANTI-SHORT CYCLE TIMER – Random Start Feature:
This feature will prevent compressor short cycling and also 
prevent multiple units in a single facility from simultaneously 
starting  following  a  power  outage. This  delay  on  break 
feature ensures that the compressor remains off, between 
cycles, until the three-minute time delay period has elapsed 
allowing system pressures to equalize before re-starting.
The random start feature, initiated after a power failure, 
will add a random time delay (between 5-120 seconds) to 
the three-minute anti short cycle time following a power 
outage. This will stagger the starting of multiple units in a 
single facility allowing a building to slowly go back on line 
when power is restored.
INDOOR COIL FREEZE PROTECTION: This feature will 
prevent the indoor coil from freeze up in the cooling mode. 
Indoor coil freeze up can occur due to a dirty air filter, low 
refrigerant charge or low room or outdoor temperatures. 
This in turn can cause compressor damage. Should a freeze