The Vert-I-Pak A series units must be installed with a free 
return  air  configuration.  The  table  below  lists  the  indoor 
airflow at corresponding static pressures. All units are rarted 
at low speed.
The Vert-I-Pak units are designed for either single speed or 
two fan speed operation. For single speed operation refer to 
the airflow table below and select the most appropriate CFM 
based  on  the  ESP  level.  Connect  the  fan  output  from  the 
thermostat to the unit on either the GL terminal for low speed 
or to the GH terminal for high speed operation.
For thermostats with two-speed fan outputs connect the low 
speed  output  to  the  unit  GL  terminal  and  the  high  speed 
output to the GH terminal.
Ductwork Preparation
Indoor Airflow Data
Fresh Air Door
If flex duct is used, be sure all the slack is pulled out of the 
flex duct. Flex duct ESP can increase considerably when 
not fully extended. DO NOT EXCEED a total of .30 ESP, as 
this  is  the  MAXIMUM  design  limit  for  the  VERT-I-PAK 
A-Series unit.
The Fresh Air Door is an “intake” system. The fresh air door 
opened via a slide on the front of the chassis located just 
above the indoor coil. Move the slide left to open and right 
to close the fresh air door. The system is capable of up to 60 
CFM of fresh air @ ~.3” H20 internal static pressure.
 
IMPORTANT: FLEX DUCT CAN COLLAPSE AND 
CAUSE  AIRFLOW  RESTRICTIONS.    DO  NOT 
USE FLEX DUCT FOR:  90 DEGREE BENDS, OR 
UNSUPPORTED RUNS OF 5 FT. OR MORE.
EXAMPLE: Measured voltage to unit (heaters) is 230 volts.  
Measured Current Draw of strip heaters is 11.0 amps.
230 x 11.0 = 2530
2530/1000 = 2.53 Kilowatts
2.53  x  3413 = 8635
Supply Air 
 
95
°
F
Return Air 
  
75
°
F
Temperature Rise 
20
°
20 x 1.08 = 21.6
8635
= 400 CFM
21.6
1 ½ TON SYSTEM ( 18,000 Btu) 
Operating on high speed @ 230 volts with dry coil
measured external static pressure .10
Air Flow = 450 CFM
In the same SYSTEM used in the previous example but 
having  a  WET  coil  you  must  use  a  correction  factor  of 
.95 (i.e. 450 x .95=428 CFM) to allow for the resistance 
(internal) of the condensate on the coil.
It is important to use the proper procedure to check external 
Static  Pressure  and  determine  actual  airfl ow.  Since  in 
the case of the VERT-I-PAK, the condensate will cause 
a reduction in measured External Static Pressure for the 
given airfl ow.
It is also important to remember that when dealing with 
VERT-l-PAK  units  that  the  measured  External  Static 
Pressure increases as the resistance is added externally 
to the cabinet.  Example:  duct work, fi lters, grilles.
Checking Approximate Airfl ow
If  an  inclined  manometer  or  Magnehelic  gauge  is  not 
available  to  check  the  External  Static  Pressure,  or  the 
blower  performance  data  is  unavailable  for  your  unit, 
approximate air fl ow call be calculated by measuring the 
temperature rise, then using tile following criteria.
KILOWATTS x 3413
=  CFM
Temp Rise x 1.08
Electric Heat Strips
The  approximate  CFM  actually  being  delivered  can  be 
calculated by using the following formula:
DO NOT simply use the Kilowatt Rating of the heater (i.e. 
2.5, 3.4, 5.0) as this will result in a less-than-correct airfl ow 
calculation.  Kilowatts may be calculated by multiplying 
the  measured  voltage  to  the  unit  (heater)  times  the 
measured current draw of all heaters (ONLY) in operation
 to obtain watts. Kilowatts are than obtained by dividing 
by 1000.
Explanation of charts
Chart A is the nominal dry coil VERT-I-PAK CFMs. Chart 
B is the correction factors beyond nominal conditions.  
Correct CFM (if needed):  
Chart B – Correction Multipli
ers
16