I. Start-up Checklist
 
Inspect all components and accessories for 
damage before and after installation.
 
Check installation for compliance with all national 
and local codes and ordinances.
 
Read and follow all manufacturer's installation 
instructions.
 
Check that circuit breaker(s) and electrical wire 
sizes are correct.  If the unit is supplied with a 
power supply cord, insure that it is stored properly.
 
Check the condensate water drain outlet(s) to 
make sure they are in compliance with all national 
and local codes, that they are adequate for the 
removal of condensate water, and that they meet 
the approval of the end user.
 
Strictly follow installation instructions concerning 
clearances around the unit.
 
Secure components and accessories, such as the 
control door and front cover.
 
Check the unit air fi lter, condenser coil and 
evaporator coil for any obstructions.
 
Check for proper operation of all components.
 
Instruct the owner or operator of the units 
operation, and the manufacturer's   
 
recommended routine maintenance schedule.  
NOTE:  It is highly recommended that a maintenance 
schedule log book be prepared for recording 
the dates and times of service.
 
Operate the unit for twenty minutes.  Record 
the unit's indoor/outdoor intake and discharge 
temperatures, amperage draw, and power voltage.
 
Assemble the Warranty Certifi cate, the Operation 
and Installation Manual, all accessory installation 
instructions and the name, address and telephone 
number of the Authorized Friedrich Warranty 
Service Company in the area for the owner or 
operator.
NOTE:  Units are to be installed, inspected, and checked by qualifi ed service personnel only.