Friedrich HEAT PUMPS ユーザーズマニュアル

ページ / 28
18
920-087-04
R
Y
W
B
GL GH
C D1 D2
F1 F2
JP1
1 2 3 4 5 6 7 8
ON
DIP
Remote Thermostat and Low Voltage Control Connections
To control the unit with a wall mounted thermostat follow 
the steps below:
1)   With the front cover removed locate the low voltage terminal 
strip at the lower portion of the Smart Center.
2)  Remove the jumper between the ‘GL’ and GH’ terminals.
3)   The control is now confi gured for control by a wall thermo-
stat. The Smart Center will no longer control the unit.
4)  If desired the accessory escutcheon kit (PDXRT) is to be 
used, install it over the existing control panel.
Note: To revert back to the Smart Center control of the unit replace 
the jumper wire between the ‘GL’ and ‘GH’ terminals that was 
removed in step 1.
Thermostat Connections
 C  = Common 
Ground
  W  =  Call for Heating
  Y 
=  Call for Cooling
  R  =  24V Power from Unit
  GL  =  Call for Low Fan
  GH  =  Call for High Fan
  B 
=  Reversing Valve Energized in heating mode 
   
 
(PDH Models Only)
*If only one G terminal is present on thermostat connect to GL 
for low fan or to GH for high fan operation.
Remote Thermostat
All Friedrich PD model PTAC units are factory confi gured to be 
controlled by either the chassis mounted Smart Center or a 24V 
single stage remote wall mounted thermostat.  The thermostat 
may  be  auto  or  manual  changeover  as  long  as  the  control 
confi guration matches that of the PTAC unit. 
Figure 13  
Control board with optional PDXRT escutcheon kit installed