PTAC Installation Recommendations
For proper PTAC unit performance and maximum operating life please refer to the minimum installation clearances below:
The above suggestions are for reference only and do not represent all possible installations. Please contact the factory for 
information regarding affects of other installation arrangements. By following these simple recommendations you can be 
confi dent that your Friedrich PTAC will provide years of worry free operation.
PTAC
SHRUB
POLE
FENCE OR WALL
PTAC
PTAC
TYP. BUILDING ( PLAN VIEW )
CONDENSING UNIT
12"
36"
36"
36"
36" MIMUMUM, MAJOR 
OBSTRUCTIONS
12" MINIMUM, MINOR 
OBSTRUCTIONS
Figure 2
PTAC units should be installed 
no closer than 12" apart when 
two units are side by side. If 
three or more PTAC units are to 
operate next to one another allow 
a minimum of 36" between units. 
Also, a vertical clearance of 60" 
should be maintained between 
units installed.
Figure 1
BETWEEN PTACs
THREE OR MORE PTACs
BUILDING ELEVATION
ADJACENT 36" MINIMUM
6" MINIMUM FROM GRADE
GROUND FLOOR PTACs
TWO ADJACENT
PTACs 12" MINIMUM
WINDOW
TYP.
VIEW: OUTSIDE
60" VERTICAL MIMUMUM
12"
6"
36"
60"
For PTACs on the ground fl oor or anytime obstructions are present, use the following guidelines:
•   For minor obstructions 
such as lamp poles 
or small shrubbery a 
clearance of 12" from the 
outdoor louver should be 
maintained.
•   For major obstructions 
such as a solid fence, wall 
or other heat rejecting 
device like a condensing 
unit, a minimum distance 
of 36" should be kept.