Friedrich Digital Control Features
The new Friedrich digital PTAC has state of the art features to improve guest comfort, indoor air quality and conserve energy.  
Through the use of specifi cally designed control software for the PTAC industry Friedrich has accomplished what other Manufactur-
er’s have only attempted – a quiet, dependable, affordable and easy to use PTAC.
Below is a list of standard features on every Friedrich PTAC and their benefi t to the owner.
Digital Temperature 
Readout
By digitally monitoring desired room temperature the room is controlled more precisely than conventional systems. The large, easy 
to read LED display can show either set-point or actual room temperature as selected by owner.
One-Touch Operation
When the unit is powered off the unit can be returned directly to heating or cooling mode by pressing the ‘Heat’ or ‘Cool’ buttons 
without the confusing power up sequence of some controls. One-touch control takes guesswork out of unit control delivering a more 
enjoyable experience and eliminating front-desk calls.
Individual Mode and 
Fan Control Buttons
By having separate control buttons and indicators for both fan and mode settings the Friedrich digital control eliminates the confu-
sion of previous digital PTACs. The accurate temperature setting provides greater guest comfort than other systems.
Quiet Start/Stop
 Fan Delay
The fan start and stop delays prevent abrupt changes in room acoustics due to the compressor energizing or stopping immediately. 
Upon call for cooling or heating the unit fan will run for fi ve seconds prior to energizing the compressor. Also, the fan off delay allows 
for “free cooling” by utilizing the already cool indoor coil to its maximum capacity by running for 30 seconds after the compressor. 
Remote Thermostat 
Operation
Some applications require the use of a wall mounted thermostat. All new Friedrich PTACs may be switched from unit control to 
remote thermostat control easily without the need to order a special model or accessory kit.
Wireless Remote 
Control Ready
Guests can adjust the temperature and mode of the unit through the use of an optional hand held wireless remote, improving guest 
comfort and relaxation.
Internal Diagnostic 
Program
The new Friedrich digital PTAC features a self diagnostic program that can alert maintenance to component failures or operating 
problems. The internal diagnostic program saves properties valuable time when diagnosing running problems.
Service Error Code 
Storage
The self diagnosis program will also store error codes in memory if certain conditions occur and correct themselves such as ex-
treme high or low operating conditions or activation of the room freeze protection feature. Storing error codes can help properties 
determine if the unit faced obscure conditions or if an error occurred and corrected itself.
Constant Comfort 
Room Monitoring
The on-board processor monitors time between demand cycles (heat or cool) and will cycle the fan every 9 minutes to sample the 
room condition and determine if the desired conditions are met. This allows the room to have similar benefi ts to a remote mounted 
stat without the complication or cost of a wall mounted thermostat. 
Electronic Temperature 
Limiting
By limiting the operating range the property can save energy by eliminating “max cool” or “max heat” situations common with older 
uncontrolled systems. The new electronic control allows owners to set operating ranges for both heating and cooling independently 
of one another.
Room Freeze 
Protection
When the PTAC senses that the indoor room temperature has fallen to 40°F the unit will cycle on high fan and the electric strip heat 
to raise the room temperature to 46°F then cycle off again. This feature works regardless of the mode selected and can be turned 
off. The control will also store the Room Freeze cycle in the service code memory for retrieval at a later date. This feature ensures 
that unoccupied rooms do not reach freezing levels where damage can occur to plumbing and fi xtures.
Random Compressor 
Restart
Multiple compressors starting at once can often cause electrical overloads and premature unit failure. The random restart delay 
eliminates multiple units from starting at once following a power outage or initial power up. The compressor delay will range from 
180 to 240 seconds.
Digital Defrost 
Thermostat
The new Friedrich PTAC uses a digital thermostat to accurately monitor the outdoor coil conditions to allow the heat pump to run 
whenever conditions are correct. Running the PTAC in heat pump mode save energy and reduces operating costs. The digital 
thermostat allows maximization of heat pump run time.