PTAC Installation Recommendations
PTAC units should be installed 
no closer than 12" apart when 
two  units  are  side  by  side.    If 
three or more PTAC units are to 
operate next to one another allow 
a minimum of 36" between units.  
Also, a vertical clearance of 60" 
should be maintained between 
units  installed.    In  the  interior 
of the room the unit should be 
located a minimum of 1/4" from 
the floor and a minimum of 36" 
from the ceiling.
•  For  minor  obstructions 
such as lamp poles or small 
shrubbery  a  clearance  of 
12" from the outdoor louver 
should be maintained.
•  For major obstructions such 
as  a  solid  fence,  wall  or 
other heat rejecting device 
like  a  condensing  unit,  a 
minimum  distance  of  36" 
should be kept.
For proper PTAC unit performance and maximum operating life refer to the minimum installation clearances 
below:
For PTACs on the ground floor or anytime obstructions are present, use the following guidelines:
The above suggestions are for reference only and do not represent all possible installations.  Please contact Friedrich for information regarding affects of other 
installation arrangements.  By following these simple recommendations you can be confident that your Friedrich PTAC will provide years of worry free operation.
Figure 1
Figure 2
FRP002
PTAC
SHRUB
POLE
FENCE OR WALL
C
A
T
P
C
A
T
P
TYPICAL BUILDING ( PLAN VIEW )
CONDENSING UNIT
12"
36"
36"
36"
36" MIMUMUM, MAJOR
OBSTRUCTIONS
12" MINIMUM, MINOR
OBSTRUCTIONS
FRP001
THREE OR MORE PTACs
ADJACENT 36" MINIMUM
GROUND FLOOR PTACs
6" MINIMUM FROM GRADE
TWO ADJACENT PTACs
12" MINIMUM
TYPICAL
WINDOW
VIEW: OUTSIDE BUILDING ELEVATION
60" VERTICAL
MIMUMUM
BETWEEN
PTACs
12"
6"
36"
60"