• Exhaust Air Damper - Built in with positive closed position. 
Provides exhaust air capability to prevent pressurization of tight 
buildings. 
• Actuator Motor - 24 volt, power open, spring return with built in 
torque limiting switch. 
• Proportioning Type Control - for maximum “free cooling” economy 
and comfort. 
• Moisture Eliminator & Prefilter - permanent, washable aluminum 
construction. 
• Enthalpy Control - adjustable to monitor outdoor temperature and 
humidity. 
• Minimum Position Potentiometer - adjustable to control minimum 
damper blade position for ventilation purposes. 
• Mixed Air Sensor - to monitor outside and return air to 
automatically modulate damper position. 
 
4.3
  COMMERCIAL ROOM VENTILATOR   
        OPTIONAL 
The built-in commercial room ventilator is internally mounted and 
allows outside ventilation air, up to 50% of the total air flow rating of 
the unit, to be introduced through the air inlet openings.  It includes 
a built-in exhaust air damper.  The damper can be easily adjusted to 
control the amount of fresh air supplied into the building.  Automatic 
control shall be provided to maintain desired ventilation rate during 
the different supply airflows of fan only, Stage 1 and Stage 2 modes 
of operation. The CRV can be controlled by indoor blower operation 
or field controlled based on room occupancy using CO2 controller.  
Unit complies with ANSI/ASHRAE Standard 62.1 Ventilation for 
Acceptable Air Quality. 
 
4.4
 
ENERGY RECOVERY VENTILATOR 
 
       OPTIONAL 
 
The Energy Recovery Ventilator (ERV) shall consist of 1 or 2 rotary 
wheels in an insulated cassette frame with seals, drive motor and 
belt. The ERV assembly shall also include intake and exhaust 
blowers. The entire assembly shall easily slide in or out of the 
ventilation section, allowing for maintenance or replacement. The 
total energy wheel shall be coated with silica gel desiccant, 
permanently bonded without the use of binders or adhesives. The 
coated segments shall be washable with detergent or alkaline  coil 
cleaner and water. Desiccant shall not dissolve or deliquesce in the 
presence of water or high humidity.  All diameter and perimeter seals 
shall be provided as part of the cassette assembly and shall be 
factory set. Drive belts shall not require external tensioners or 
adjustment. Cassette wheels shall include rims to prevent belts from 
slipping off wheels.   Intake and exhaust blowers shall have 
selections of high, medium or low speed and selected independently, 
to allow for positive pressurization if  desired. The ERV cassette