Bryan Boilers Triple-Flex 150 ユーザーズマニュアル

ページ / 81
 
Date:  
8-4-2010 
 
Revision: 0 
 
Form:  
2396
 
2.2.23 M
ODBUS 
C
OMMUNICATION
 
The hydronic control Global Modbus port is a 3-
pin connector that interfaces to the following RS-
485 signals: 
 
Table 7 Modbus Terminals
Signal Terminal 
Data + 
Data - 
Common c 
 
Modbus connections can be made at the display 
(Figure 3 item 5) or the hydronic control (Figure 
7 item 24). 
 
For the modbus register map and other related 
information please download Honeywell’s 
R7910A product manual at: 
 
 
2.2.24 A
LERT 
C
ODES
 
Table 8 Alert Codes
29 
 
Code Description 
None (No alert) 
Alert PCB was restored from factory 
defaults  
Safety configuration parameters were 
restored from factory defaults 
Configuration parameters were 
restored from factory defaults 
Invalid Factory Invisibility PCB was 
detected 
Invalid Factory Range PCB was 
detected 
Invalid range PCB record has been 
dropped 
EEPROM lockout history was 
initialized 
Switched application annunciation 
data blocks 
Switched application configuration 
data blocks 
10 
Configuration was restored from 
factory defaults 
11 
Backup configuration settings was 
restored from active configuration 
12 
Annunciation configuration was 
restored from factory defaults 
13 
Annunciation configuration was 
restored from backup 
14 
Safety group verification table was 
restored from factory defaults 
15 
Safety group verification table was 
updated 
16 
Invalid Parameter PCB was detected 
17 
Invalid Range PCB was detected 
18 
Alarm silence time exceeded 
maximum 
19 
Invalid safety group verification table 
was detected 
20-26 RESERVED 
27 
Safety processor was reset 
28 
Application processor was reset 
29 
Burner switch was turned OFF 
30 
Burner switch was turned ON 
31 
Program Module (PM) was inserted 
into socket 
32 
Program Module (PM) was removed 
from socket 
33 
Alert PCB was configured 
34 
Parameter PCB was configured 
 
35 Range PCB was configured 
36 
Program Module (PM) incompatible 
with product was inserted into socket 
37 
Program Module application 
parameter revision differs from 
application processor 
38 
Program Module safety parameter 
revision differs from safety processor 
39 
PCB incompatible with product 
contained in Program Module 
40 
Parameter PCB in Program Module is 
too large for product 
41 
Range PCB in Program Module was 
too large for product 
42 
Alert PCB in Program Module was 
too large for product 
43 
IAS start check was forced on due to 
IAS enabled 
44 
Low voltage was detected in safety 
processor 
45 
High line frequency occurred 
46 
Low line frequency occurred 
47 
Invalid subsystem reset request 
occurred 
48 
Write large enumerated Modbus 
register value was not allowed 
49 
Maximum cycle count was reached 
50 
Maximum hours count was reached 
51 
Illegal Modbus write was attempted 
52 
Modbus write attempt was rejected 
(NOT ALLOWED)